14 Appendix - Message and fault code list
Note: Reboot can either be made from PC computer or by power off-on.
Status messages
No:
Description
-
-
Power
up
N n
Run mode (
nn
= station number)
Lo
Program load mode state.
Flashing ”Lo”, ready for self programming (program found in other unit).
HA
(SR11=7)
Program execution stopped from PC computer or not started after program download.
Can be started either from PC or by power off-on.
UE
Application specific user error, controlled by SR_PlutoDisplay in the PLC program.
User faults
No:
Fault and possible reason.
Reset action
Er10* Dynamic output short circuited to foreign voltage.
Automatically reset
Er11* IQ_ for illuminated push button function. Missing diode.
Automatically reset
Er12* Short circuit between two dynamic inputs.
Automatically reset
Er13* Static output Q10..17 (Q20..27) short circuited to 0V or
overloaded.
Automatically reset,
“K” button
Er14* Static output Q10..17 (Q20..27) short circuited to 24V.
Automatically reset
Er15 Power supply below 18V.
Autom. 3 min or ”K” button
Er16 Power supply above 30V.
Autom. 3 min or ”K” button
Er17 Power supply below 15V. Critically low.
Autom. 3 min or ”K” button
Er18 CAN-bus fault. (Short circuit, termination resistor, etc.)
Autom. 3 min or ”K” button
Er19
Other unit with same station number on Can-bus.
Er20 PLC-program not loaded.
Load of PLC program
Er21 PLC-program
CRC-error.
Reload with valid PLC-program
Er22 IDFIX problem. External IDFIX can not be read.
Reboot (Replace IDFIX)
Er23 Unmatched ID. IDFIX doesn’t match declaration in
program.
Exchange of identifiers or re-
declaration of identifier in
program.
Er24 Erroneous PLC-code. Invalid PLC-instructions.
Reload with valid PLC-program
Er25
For versions as B16 or B22. Non existing output used in
program.
Er26
Baud rate conflict. Unit programmed for other baud rate
than current bus baud rate.
Note that Pluto must be rebooted after change of
baudrate in the PLC program.
Reprogramming or reboot
Er27 Wrong checksum for unit member in common program.
Reprogramming or reboot
Er28
PLC program does not match the Pluto family.
Families: [A/B/S/D 20, 16, 22], [B/S/D 45, 46], [Pluto AS-
i, B42 AS-i]
Change to other type of Pluto
or change the program.
Er29 Unsupported program version. The program contains
instructions only supported by later customer specific
operating systems. **(See below)
Update of operating system
Er30 Unsupported function block used. **(See below)
Update of operating system
Er31 IDFIX-PROG program mismatch.
Load program to flash memory
with ”K” button.
*Combined with LED flashing for the affected I/O.
**Additional information can be retrieved via Pluto Manager.