Inputs and outputs for Pluto O2
Terminal on Pluto
In-/Output name in software
I/O type
Local/Global
I0, I1
I_.0, I_.1
Safe Input (for monitoring)
Global
Q0.13…Q0.34
Q_.0
Safe Output (Relay)
Global
Q1.13…Q0.34
Q_.1
Safe Output (Relay)
Global
IQ10, IQ11
I_.10, I_.11
Safe Input
Global
Q_.10, Q_.11
Nonsafe Output
Local
where “_” is the Pluto number
Pluto O2 is a safety output module with two relay output groups with three contacts each. Pluto
O2 is also equipped with two safe inputs for monitoring and two combined safe in-/non-safe
outputs (IQ).
4.1 I.. Digital
failsafe
inputs
Each input is separately
connected to both processors
which, facilitating both single
channel and dual channel safety
devices.
The inputs can be supplied by
+24V or by the dynamic signal
outputs A, B or C.
CL
I0
CH
ID
Pluto O2
IQ10
Q1
B
IQ11
33
A
13
14
+24V 0V
CSh
23
24
34
B
33
34
13
14
23
24
A
Q0
I1
250VAC, 5A
24V, 1.5A
24V, 1.5A
250VAC, 5A
Power supply
Safety Output Module
Safe inputs
Non-safe outp
Dynamic outp
Safe inputs
Non-safe outp
Dynamic outp
I/O overview PLUTO O2