46
2TLC172001M0211_A
Safety output
Q2, Q3:
Solid state, -24V DC, 800mA
Output voltage tolerance:
Supply voltage -1.5V at 800mA
Q0, Q1, (Q4, Q5):
Relay, AC-12: 250 V / 1.5 A
AC-15: 250 V / 1.5 A
DC-12: 50 V / 1.5 A
DC-13: 24 V / 1.5 A
Pluto O2: Q0, Q1:
13-14, 23-24
Relay, AC-12: 250 V / 5 A
AC-15: 250 V / 3 A
DC-12: 60 V / 5 A
DC-13: 24 V / 3 A
33-34
Relay, AC-12/AC-15/DC-12/DC-13: 24 V / 1.5 A
Outputs, non-failsafe
IQ10, IQ11,..
Solid state +24V, PNP open collector
Also configurable as failsafe inputs.
Max load/output:
800 mA
Max total load:
A20, B16, B20, S20, B22, D20
IQ10..17: 2.5 A
B46, S46, D45, B42 AS-i
IQ10..17: 2 A, IQ20..27: 2A
Pluto AS-i
IQ10..13: 2 A
Current monitoring IQ16, IQ17 (Only Pluto A20)
Range
0-1.0 A
Accuracy
10%