24
PCS100 UPS-I
User Manual
Nominal ratings
Rated power (kVA)
Rated power (kVA) at rated voltage and power factor.
Inverter Rated Current
Rated inverter current available during PCS100 UPS-I
discharge mode
Utility Disconnect Rated Current
Rated UD current during PCS100 UPS-I online mode
Overload ratings
Inverter
110% of rated current for 30 s
Utility Disconnect
120% of rated current for 60 s every 10 minutes
150% of rated current for 30 s every 10 minutes
200% of rated current for 10 s every 10 minutes
300% of rated current for 5 s every 10 minutes
Table 3-3: PCS100 UPS-I model range table definition explanations