PCS100 UPS-I
User Manual
81
Range:
True / False
Setting Up:
Select “True” to clear the PQ events. The parameter will automatically return to “False”
once the events have been cleared.
Note:
This parameter does not clear the events recorded in the Event Log.
Parameter:
053 Set Parameter
Function:
Provides the ability make a custom adjustment to an internal parameter
Access:
Continuous
Setting Up:
Enter the factory supplied code to change the required internal parameter. When a
correct code is entered the message "Parameter Write Result = OK" will be displayed.
If an incorrect code is entered the message "Sorry, value entered is not correct" is
displayed.
This parameter can also be accessed via the Remote Web Pages
–
see section 12.2.
Note:
The code must be entered exactly. Take care when emailing such codes. Different
characters look the same in some fonts. E.g. the lower case letter L looks the same as the
numeral one in Times New Roman Font. The Arial Font is OK.
Parameter:
061 Show Faults
Function:
Shows all the faults and warnings presently active
Access:
Tech
Note:
Sometimes there can be more than 1 fault or warning active at one time. The most critical
fault is displayed on the Status line. This screen shows all the faults and warnings
presently active.
Table 10
-
2: Menu 000 General parameters