Step 8 - Initial Startup
Verify that all AC, DC, GND and Controller connections are complete and secure.
Using a multimeter, Verify plant reference ground and chassis ground resistance to side ground bar is less than
0.1 Ohms. With rectifiers and converters unplugged as well as all load breakers on and AC breakers off, verify
resistance of battery bus to ground is greater than 1M
Ω.
If being operated as an ungrounded system, verify both
positive and negative bus measurement to each other and ground is greater than 1M
Ω.
Turn on AC input breakers. If there are no alarms, make required adjustments to the default settings on the
controller for this installation.
Step 9 - Configure Controller
Verify and edit controller basic configuration parameters per site engineering instructions.
Refer to Galaxy Pulsar Plus Product Manual for additional information.
Information: Controller Default Voltage Settings
Parameter
Range
Valve-Reg (Default)
Flooded
NiCd
Rectifier Float Selective High Voltage Shutdown
-50 to -60V
58.50
58.50
58.50
High Float Voltage Major Alarm
-50 to -60V
57.00
57.00
57.00
High Float Voltage Minor Alarm
-50 to -60V
56.00
56.00
56.00
Rectifier/System Float Voltage
-42 to -56.5V
54.48
52.08
54.40
Battery on Discharge Float Alarm
-46 to -55V
51.00
50.00
51.00
Very Low Float Voltage Alarm
-40 to -51V
46.00
46.00
46.00
Rectifier On Threshold
-40 to -51V
44.00
44.00
44.00
Information: AC Cord Options
IEC-Style, 8ft, 12AWG
Part Number
Plug
Length
CC848847368
No plug
8 ft
CC848850792
5-15P
8 ft
CC848850801
5-20P
8 ft
CC848850826
6-15P
8 ft
CC848850834
6-20P
8 ft
CC848850842
L6-20P
8 ft
850044361
L5-15P
15 ft
850044362
L5-20P
15 ft
CC848895961
L6-20P
15 ft
Molex mini-fit SR-Style, No Plug
CC848822420
(2) 15 ft., 3X8AWG
848710711
(2) 10 ft., 3X8AWG
CC848830522
(2) 4 ft., 3X8AWG
CC848773515
15 ft., 10AWG SO Cord
CC848906586
10 ft., 8AWG, SO Cord
Information: Battery Monitoring Connections
Battery Monitoring is accomplished with a “Daisy Chained” series of probes connected to J2. The Probes monitor
battery temperature and voltage (ES771 required to monitor voltage). Bolt the Probe under the “–“ terminal
connector hardware; NOT under the connecting lug.
Temperature Measurement
Temperature and Voltage Measurement