QUICK START GUIDE
Step 4 - Connect Batteries and DC
Output to Loads
The figure to the right shows the DC circuit of
the system.
Battery connections may be made to bullet-style
distribution positions configured as Battery
Breaker Positions or direct to the battery bus.
Caution:
Verify battery voltage and polarity with a
voltmeter before connecting.
Load connections are made to bullet-style
distribution positions configured as Load
Breaker Positions.
Distribution panels are each equipped with 20
(19” panel) or 26 (23” panel) bullet-style
distribution positions. Each position is selectable
between battery input or load output.
Breaker sizes up to 250A, TPS fuses to 70A and
GMT fuses to 12A are available.
Lug Landings
Distribution
Battery Bus
Landings
1/4-20 studs on 5/8” centers
Lug tongue width 0.68” max
5/16-18 studs on 1”
centers
Torque
65 in-lb - 7/16” socket
160 in-lb - 1/2” socket
Two multi-pole adapters are required for each multi-pole breaker - see illustration, right
Multi-Pole Adapter Kits - 2 required per breaker
CC848756916
850021775
850021955
Poles
2
2
3
Lug Landings
1/4” x 5/8”
3/8” x 1”
3/8” x 1”
Protector
Alarm Pin (up)
+24V Protector
Note Orientation
-48V Protector positions
Blue Terminals
Lower positions
+24V Protector positions
Orange Terminals
Upper positions
-48V Protector
Note Orientation
Protector Alarm Pin (up)
Load Bus
Return Bus
Orange
+24 VDC Bus
Blue
-48 VDC Bus