![ABB MTQ22-FBP.0 Скачать руководство пользователя страница 31](http://html.mh-extra.com/html/abb/mtq22-fbp-0/mtq22-fbp-0_manual_2750031.webp)
—
Technical data
—
General
Supply voltage
24 V DC (+30 % ... -20 %)
(19.2 ... 31.2 V DC) including ripple
Current consumption
Max. 180 mA (at 19.2 ... 31.2 V DC)
Short-circuit protection at port 1 ... 4
PTC resistor
Reverse polarity protection of supply inputs
Yes
Pollution degree terminals
3
Mounting
Snap-on mounting onto 35 mm standard mounting rails
Mounting Position
Any
Degree of protection
IP20
Temperature range: Storage / Operation
-25 ... +70 °C / 0 ... +60 °C
Dimensions (W x H x D)
45 mm x 90 mm x 96 mm
Total power dissipation
max. 3.5 W
Net weight
0.172 kg
Configuration
Via PC tool
Diagnosis with LEDs
See section "Diagnosis"
Cable length between MTQ22-FBP.0 and devices
It is strongly recommended to limit the cable length to 3 m
Marks, Approvals
CE, cUL
Further in preparation. Ask your local sales unit representative for other
marks/approvals.
Operation altitude above sea level
max. 2000 m
For higher altitudes please contact your local sales unit.
—
EMC
Measurement of radiated and conducted interference
according to EN61131-2 CISPR16-2-3
Class A
Electrostatic discharge
according to IEC 61000-6-2
8 kV air discharge
6 kV contact discharge
Radio frequency electromagnetic field
according to IEC 61000-4-3
10 V/m
Fast transient bursts
according to EN61000-4-4
2 kV power supply
0.5 kV communication lines
High energy surges
according to EN61000-4-5
1/0.5 kV CM/DM power supply
Conducted radio frequency interference
according to EN61000-4-6
10 V
Immunity low frequency harmonics
according to EN61000-4-11
Power supply: 50 ... 12 kHz, 3 V
31
U N I V ER S A L M OTO R CO N T R O L L ER U M C 10 0. 3 |
MTQ2 2- FB P.0 MODBUS TCP M A N UA L