Data Access in one block ordered by data type
This section explains how to access the data of the connected devices in one block. Only one Modbus TCP read request is
required to read all monitoring data, and only one request is necessary to write all command data.
Monitoring Data
This address map shows how the complete monitoring data from up to four UMCs can be read in one block. The data is
ordered without any gaps after each other in the following way.
DI
UMC1
DI
UMC2
DI3
UMC3
DI4
UMC4
AI1
UMC1
...
AI
UMC4
Diag
UMC1
...
Diag
UMC4
The following table shows in detail how the data is organized:
UMC at
port 1
UMC at
port 2
UMC at
port 3
UMC at
port 4
Data
0x5000
dec
20480
0x5001
dec
20481
0x5002
dec
20482
0x5003
dec
20483
Summary
Warning
Summary
Fault
Local
Control
Rev
Lockout
Time
Overload
warning
Run Fwd /
Opening
Off
Run Rev/
Closing
UMC100
DI5
UMC100
DI4
UMC100
DI3
UMC100
DI2
UMC100
DI0
UMC100
DI0
Run Fast
Fwd
-
0x5004
dec
20484
0x500B
dec
20491
0x5012
dec
20498
0x5019
dec
20505
Motor current in % of I
e
(0 % - 800 %
0x5005
dec
20485
0x500C
dec
20492
0x5013
dec
20499
0x501A
dec
20506
Analog word (Thermal Load: 0 % - 100 %)
0x5006
dec
20486
0x500D
dec
20493
0x5014
dec
20500
0x501B
dec
20507
Analog word (Time to trip in seconds)
0x5007
dec
20487
0x500E
dec
20494
0x5015
dec
20501
0x501C
dec
20508
Analog word (Time to restart in seconds)
0x5008
dec
20488
0x500F
dec
20495
0x5016
dec
20502
0x501D
dec
20509
Analog word (Active power in selected scale)
0x5009
dec
20489
0x5010
dec
20496
0x5017
dec
20503
0x501E
dec
20510
DX1xx DI7
DX1xx DI6
DX1xx DI5
DX1xx DI4
DX1xx DI3
DX1xx DI2
DX1xx DI1
DX1xx DI0
-
-
Run Time
Exceeded1
Out of
Position
Torque
Open
Torque
Closed
End Pos
Open
End Pos
Closed
0x500A
dec
20490
0x5011
dec
20497
0x5018
dec
20504
0x501F
dec
20511
U Imbal.
warn
U Imbal.
trip
Under-
voltage
warn
Under-
voltage
trip
Under-
power
warn
Under-
power trip
Over-
power
warn
Over-
power trip
Earth fault
warning
Earth fault
trip
Cooling
time
running
-
THD
warning
No start
possible
One start
left
More than
one start
left
0x5020
dec
20512
0x5024
dec
20516
0x5028
dec
20520
0x502C
dec
20524
CB
missing
PTC wiring
failure
PTC hot
Pre-warn
therm.
mode
Locked
rotor
Phase
imbalance
Phase loss
Thermal
OL trip
Actuator
problem
UMC self-
test erro
Earth fault
pre-
warning
Eart fault
trip
I > warning
threshold
I > trip
threshold
I <
warning
threshold
I < trip
threshold
0x5021
dec
20513
0x5025
dec
20517
0x5029
dec
20521
0x502D
dec
20525
Trip/
Warning
from
AuxFault
fb input 5
Trip/
Warning
from
AuxFault
fb input 4
Trip/
Warning
from
AuxFault
fb input 3
Trip/
Warning
from
AuxFault
fb input 2
Trip/
Warning
from
AuxFault
fb input 1
HW fault
on IO
module
Custom
applica-
tion error
IO module
missing
-
-
-
-
Trip
triggered
from
Multif.
input DI2
Trip
triggered
from
Multif.
input DI1
Trip
triggered
from
Multif.
input DI0
Trip /
Warning
from
AuxFault
fb input 6
0x5022
dec
20514
0x5026
dec
20518
0x502A
dec
20522
0x502E
dec
20526
-
-
THD
Warning
Voltage
out of
spec
1
Overload
power
Underload
power
1
-
-
-
-
Cooling
Time
Running
Just one
start left
Num
Starts
Overrun
-
-
-
0x5023
dec
20515
0x5027
dec
20519
0x502B
dec
20523
0x502F
dec
20527
Ext.
diagnosis
is
available.
Parameter
out of
range
-
-
-
-
-
-
Fault code
27
U N I V ER S A L M OTO R CO N T R O L L ER U M C 10 0. 3 |
MTQ2 2- FB P.0 MODBUS TCP M A N UA L