Reading and Writing Device Data
The following tables show how to generally access data of the devices connected to port one to port four of the
MTQ22-FBP.0. The manuals of the connected devices are also needed to understand what data is provided and to derive the
length of the input and output data telegrams from it.
The tables in this document show the mapping of the most common input, output and diagnosis data, that can be accessed
very fast with one single read or write command.
Generally it is possible to read all data from the UMC100.3. All registers are listed in the separate document
2CDC135068M0201, that can be downloaded from the ABB product web page.
In the following tables the same data types are shown in the same color for an easier identification.
Individual data access by device
This method makes it possible to individually access data from a connected device via single registers or groups of registers
organized in words.
Address for data access to device
connected to port
Data
Length
Access
1
2
3
4
0x0C00
dec 3072
0x0C20
dec 3104
0x0C40
dec 3136
0x0C60
dec 3168
Diagnosis data of
connected device
0 ... 16 registers*
Read
0x1000
dec 4096
0x1010
dec 4112
0x1020
dec 4128
0x1030
4144
Digital Inputs (DI)
0 ... 16 registers*
(0 - 32 bytes)
Read
0x1800
dec 6144
0x1810
dec 6160
0x1820
dec 6176
0x1830
dec 6192
Digital Outputs
(DO)
0 ... 16 registers*
(0 - 32 bytes)
Write, Read
0x2000
dec 8192
0x2100
dec 8448
0x2200
dec 8704
0x2300
dec 8960
Analog Inputs (AI)
0 ... 256 registers
Read
0x2800
dec 10240
0x2900
dec 10496
0x2A00
dec 10752
0x2B00
dec 11008
Analog Outputs
(AO)
0..256 registers
Write, Read
*) Actual number of registers (length) depends on the connected device.
The following table shows the data which can be accessed using bit access requests.
Address for data access to device
connected to port
Data
Length
Access
1
2
3
4
0x1000
dec 4096
0x1100
dec 4352
0x1200
dec 4608
0x1300
dec 4864
Digital Inputs (DI)
bitwise access
0 ... 256 Bit*
Read Coils,
Read Multiple Coils
0x1800
dec 6144
0x1900
dec 6400
0x1A00
dec 6656
0x1B00
dec 6912
Digital Outputs
(DO) bitwise access
0 ... 256 Bit*
Write Coils,
Write Multiple Coils
Read Coils,
Read Multiple Coils
*) Actual number of bits depends on the connected device.
19
U N I V ER S A L M OTO R CO N T R O L L ER U M C 10 0. 3 |
MTQ2 2- FB P.0 MODBUS TCP M A N UA L