2.8 IP Protection and designation

The housing for the MT-series transmitters is certified as con-
forming to protection type IP67 (according to IEC 60529) or Type 
4X (according to NEMA 250).

2.9 Cable connection

The electrical connection is established via a cable entry, ½-4 

NPT thread, or by M20 adapter.

2.11 Protective grounding

All transmitters are supplied with an external ground connection for 
protective grounding. Wire this ground connection to a suitable earth 
ground. For a transmitter measuring loop, an earth ground should 
maintain a resistance of 5 ohms or less. Use a heavy-duty conductor, at 
least 15 AWG / 1.6mm2 Ø. 

                IMPORTANT NOTE

                With  Category  3  transmitters  for  use  in  “Zone  2”,  a 
qualified  cable  gland  for  this  type  of  protection  must  be  in-
stalled by the customer (see the Hazardous Area Consideration 
section).  For  transmitters  with  a  flame-proof  enclosure  (Ex  d) 
type  of  protection,  the  housing  cover  must  be  secured  using 
the locking screw. The screw plug that may have been supplied 
with the transmitter must be sealed at the plant using Molykote 
DX.  The  installer  assumes  responsibility  for  any  other  type  of 
sealing  medium  used.  Increased  force  is  required  to  unscrew 
the housing cover after an interval of several weeks. This is not 
caused by the threads but is due to the type of gasket. 

                  CAUTION

                • The cable entry device shall comply with the require-
ments of EN 60079-0 and maintain IP 54 or better as required by 
the installation conditions. 

• Field wiring should be rated at least 10°C above the maximum 
ambient temperature 

2.10 Grounding

A terminal is available on both the outside of the housing and in 

the plug for grounding (PE) the transmitter. Both terminals are 

electrically connected to one another (see Figure 2-12).

Figure 2-12 — Ground connection on transmitter housing

Ground
Screw

                     WARNING – General Risks. 

                    A protective grounding connection is absolutely
                    necessary to ensure personnel protection, to protect 
against surge (in case of installation of this option) and to pre-
vent explosions in potentially explosive environments.

2.12 General guidelines 

                     WARNING

                     Make sure all circuits are de-energized prior to
                     installation.

The MT-series has been evaluated as an Installation (Over-
voltage) Category 1/Pollution Degree 2 apparatus, per IEC 
61010

The maximum altitude of operation is 6560 feet (2000 me-
ters).

The MT-series is designed with both internal and external 
protective earth (ground) terminals.

All field wiring connected to the MT-series transmitters must 
comply with National Electric Code or any other applicable 
regional electric codes.

2.13 Flame-proof/explosion-proof installations

2.13.1 Installation requirements

The MT-series of level transmitters is designed for use in Division 1 
or at the boundary of a Zone 0 and Zone 1 hazardous area. 

                 CAUTION

                

The flameproof joints of the equipment are not intend-

ed to be repaired. Consult the manufacturer if repair of the 
flameproof joints is necessary. 

                  CAUTION 

                

• The cable entry device shall comply with the requirements of

                   EN 60079-0 and maintain IP 54 or better as required by the 
installation conditions. 

• Field wiring should be rated at least 10°C above the maximum ambi-
ent temperature 

Cable or conduit entries must be fitted with a suitably certified cable 
entry device, with or without the use of a suitably approved thread 
adaptor. Where conduit is used in the installation, a conduit seal is 
not required immediately after the end-user field wiring entrance. 

Installation and use of apparatus in hazardous locations shall be in 
accordance with an IEC 60079-14 or applicable regional standards.

                  CAUTION 

                  

The housing cover can only be removed when the unit 

is installed in a non-hazardous area, when installed with intrinsic 
safety barrier, or when power is removed from the transmitter.

                       WARNING – Bodily Injury. 

                       General risks. Cable, cable gland and unused port
                       plug  must  be  in  accordance  with  the  intended 
type  of  protection  (for  example,  intrinsically  safe  and  explo-
sion-proof)  and  the  degree  of  protection  (for  example,  IP6x 
according to IEC EN  60529 or NEMA 4x). See also the adden-
dum for Ex Safety Aspects and IP Protection. In particular, for 
explosion-proof installation, remove the red, temporary plas-
tic cap and plug the unused opening  with a plug certified for 
explosion containment.

Содержание MT series

Страница 1: ...information Overview Electrical installation and ratings Explosive atmosphere markings Special conditions of use Routine maintenance tests Installation drawings EU declaration of conformity Certification for SIL 3 Capable State of the art loop powered 4 20 mA output guided wave radar transmitter for liquid level applications K TEK Products ...

Страница 2: ...sive Atmosphere markings 6 3 1 IECEx IS markings 6 3 2 IECEx Flameproof markings 6 3 3 FM US HazLoc markings 7 3 4 CSA Canada HazLoc markings 7 4 Safety informa on for inspec on and maintenance 8 4 1 Personnel qualifica ons 8 4 2 MT5X00 Alarm Levels and Dangerous Undetected Failure Rates Calcula on 8 4 3 Alarm Levels to be Programmed in Logic Solver 8 4 4 Use of Cri cally Restricted CR Mode for Saf...

Страница 3: ...ctrical systems and the relevant standards regulations and guidelines concerning explo sion protection 1 4 Information on WEEE Directive 2002 96 EC Waste Electrical and Electronic Equipment This product solution is not subject to the WEEE Directive 2002 96 EC or corresponding national laws e g the ElektroG Electrical and Electronic Equipment Act Germany Dispose of the product solution at a special...

Страница 4: ...lowing as part of a regular inspection Pressure bearing walls lining of the level device Measurement related function Leak tightness Wear corrosion 2 4 Operator liability In instances where corrosive and or abrasive materials are be ing measured the user must check the level of resistance of all parts that are coming into contact with these materials ABB offers guidance in the selection of materia...

Страница 5: ...ive environments 2 12 General guidelines WARNING Make sure all circuits are de energized prior to installation The MT series has been evaluated as an Installation Over voltage Category 1 Pollution Degree 2 apparatus per IEC 61010 The maximum altitude of operation is 6560 feet 2000 me ters The MT series is designed with both internal and external protective earth ground terminals All field wiring c...

Страница 6: ...ll be fitted to the input terminals Refer to ABB Instruction docu ment The cable entry device shall comply with the requirements of IEC 60079 0 and maintain IP 54 or better b Conditions of Manufacture Equipment with ic ia intrinsic safety shall be fitted with the MT Series Hermetic Seal Adapter Conditions of Certification a Special Conditions for safe use When EPL Ga or Da is required for example ...

Страница 7: ...e electrical equipment produced complies with the documentation Conditions of Certification a Special Conditions for safe use For explosion proof and Division 2 models with the symbol Ex ia and the words Associated Equipment always open circuit before removing covers For Intrinsically Safe models with the symbol Ex ia and the words INTRINSICALLY SAFE installations shall comply with the installatio...

Страница 8: ... by setting of diagnostic bits in HART protocol output 4 All MT5000 FMEDA analysis is based on using a safety accuracy of 2 5 The internal diagnostics are designed to achieve a Safe Failure Fraction of 90 minimum 6 The target average probability of failure on demand is less than 1 5 x 10 3 7 MT5000 transmitters are qualified for use in a SIS only when the output used for the safety function is the...

Страница 9: ...or remove it from service based on an LCD failure 4 7 3 Output Checkout The MT5000 can be equipped to provide level indication through the 4 20mA output HART communications and Foundation Fieldbus Only transmitters that are specified to output 4 20mA may be used in a Safety Implemented System The HART communication capabil ity of the 4 20mA transmitter will only be used for configuration and proof...

Страница 10: ...cement 4 8 Verify Proper Power up of the Transmitter Use a mA meter to measure the output current When power is applied the output should go to 4 00 mA for at least 1 second and then to either the measured level or an alarm condition out put If this does not happen the transmitter may not be receiv ing enough power or the main electronic is defective Excessive current above 21 mA is also an indica...

Страница 11: ... can be found on the web site at https library abb com and searching for certificate Exida SIL ABB 16 12 C118 C001 MT5000 Series IMPORTANT NOTE The user is responsible of verifying that current failure rates shown on the certificate meet the Safety Instrumented Function SIF ...

Страница 12: ...12 7 Typical Wiring Drawing ...

Страница 13: ...13 8 Installation Drawings for Intrinsic Safety Standard Wiring Reference ABB drawing ELE9021 MT5000 Series Intrinsically Safe Electrical Interconnection Diagram ...

Страница 14: ...14 8 Installation Drawings for Intrinsic Safety Standard Wiring Reference ABB drawing ELE1034 MT5000 Series FM CSA Intrinsically Safe Electrical Interconnection Diagram ...

Страница 15: ...make technical changes or modify the contents of this document without prior notice With regard to purchase orders the agreed particulars shall prevail ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure...

Отзывы: