5 - Troubleshooting
B
ehavior of a system with leakage
If the voltage measured between one of the two poles and ground does not tend to 0V and
stabilizes on a value, there is a ground leakage from the photovoltaic module.
([DPSOH :KHQ WKH PHDVXUHPHQW LV PDGH EHWZHHQ SRVLWLYH SROH DQG JURXQG RQ D
SKRWRYROWDLFPRGXOHZLWK9RF 9DYROWDJHRI9LVPHDVXUHG
M
easuring the insulation resistance of the PV module
To measure the insulation resistance of the photovoltaic module compared to ground, the two poles of the PV
generator must be short-circuited (using a suitably sized selector), and verify that the chassis of the module
itself is referred to ground (of the inverter).
Once the short-circuit has been made, measure the insulation resistance (Riso) using a megohmmeter posi-
tioned between the two shorted poles and ground (of the inverter).