I.L. 40-385.5
A-15
Apply a rated dc voltage to RCVR #1 terminals
TB 5/7 (+) and TB 5/8(-). Repeat the test. The re-
lay should not trip.
b. POTT/PUTT Systems Only
Change the STYP setting to POTT. Apply a for-
ward fault as shown in the Non-Pilot Mainte-
nance test, Step 5. The relay should not trip.
Apply a rated dc voltage to RCVR #1 terminals
TB 5/7(+) and TB 5/8(-). Repeat the test. The re-
lay should trip.
2.3
Single-Pole Trip Test
2.3.1
Output Contact Test (Phases B and C)
Step 1.
Set relay for Non-Pilot systems (Table A-
1) or for Pilot systems per Section 2.2.2. Check
the 62T setting; it should be 5.000.
For a Pilot system, change the PLT setting to
YES, and apply rated dc voltage to Pilot enable
terminals TB 5/9(+) and TB 5/10(-). Also, apply a
rated voltage to RCVR #1 terminals TB 5/7(+)
and TB 5/8(-) if the STYP = POTT or PUTT; set
TTYP = SPR.
Step 2.
Repeat Non-Pilot Maintenance test, step
5 for trip and BFI. Check the contact closures for
Trip A, &BFIA (AG fault), Trip B & BFIB (BG fault)
and Trip C & BFIC (CG fault).
2.3.2
Input Opto-Coupler Check
NOTE: Before applying any voltages, check the
jumper positions on the Interconnect
module. The JMP7 and JMP9 should be
“IN” for the XTRIPB application.
Step 3.
XTRIPA Terminals.
(a) Set IM = 5 and SPTT = 6. Apply a rated dc volt-
age to XTRIPA terminals TB5/1(+) and TB5/2(-).
Apply an AG fault with Ia = 4.5 amps and
Va = 30 volts as shown in the test step 5 of the
Non-Pilot Maintenance Test. The relay should
trip in 5 seconds with a display of 62T.
(b) Change the setting of IM from 5 to 2. Repeat the
test 3(a). The relay should trip in 4 cycles with a
display of CIF.
Step 4.
XTRIPB Terminals.Set IM = 5. Apply a
rated voltage to XTRIPB terminals TB5/13(+) and
TB5/14(-). Repeat step 3(a) except apply a BG
fault.
Step 5.
XTRIPC Terminals. Repeat step 3(a) ex-
cept apply a voltage to XTRIPC terminals TB5/
11(+) and TB5/12(-) and apply a CG fault. Reset
IM = 1 and SPTT = 1.
Содержание MDAR
Страница 84: ......
Страница 88: ...I L 40 385 5 A 16 Figure A 1 Test Connection for Single Phase to Ground Faults Sheet 1 of 4 1502B51 Sub 1 ...
Страница 89: ...I L 40 385 5 A 17 Figure A 2 Test Connection for Three Phase Faults 1502B51 Sub 1 Sheet 2 of 4 ...
Страница 90: ...I L 40 385 5 A 18 Figure A 3 Test Connection for Phase to Phase Faults 1502B51 Sub 1 Sheet 3 of 4 ...
Страница 96: ......
Страница 98: ...I L 40 385 5 A 26 I L 40 385 5 A 26 I L 40 385 5 A 26 Figure 5 MDAR REL 300 Relay Assembly sub 3 1502B21 ...
Страница 101: ......
Страница 102: ......
Страница 104: ......
Страница 105: ...I L 40 385 5 A 33 I L 40 385 5 A 33 I L 40 385 5 A 33 Figure 15 MDAR REL 300 Zone 1 Trip Logic sub 1 9659A66 ...
Страница 106: ...I L 40 385 5 A 34 I L 40 385 5 A 34 I L 40 385 5 A 34 Figure 16 MDAR REL 300 Zone 2 Trip Logic sub 1 9659A67 ...
Страница 107: ...I L 40 385 5 A 35 I L 40 385 5 A 35 I L 40 385 5 A 35 Figure 17 MDAR REL 300 Zone 3 Trip Logic sub 1 1504B04 ...
Страница 111: ......
Страница 112: ...I L 40 385 5 A 40 I L 40 385 5 A 40 I L 40 385 5 A 40 Figure 25 Load Loss Accelerated Trip Logic sub 2 1504B29 ...
Страница 116: ......
Страница 118: ...I L 40 385 5 A 46 I L 40 385 5 A 46 I L 40 385 5 A 46 Figure 35 Power Reversal sub 1 9654A17 ...
Страница 119: ...I L 40 385 5 A 47 I L 40 385 5 A 47 I L 40 385 5 A 47 Figure 36 Reverse Block Logic sub 1 9659A73 ...
Страница 120: ...I L 40 385 5 A 48 I L 40 385 5 A 48 I L 40 385 5 A 48 Figure 37 Unequal Pole Closing on Fault sub 1 9654A29 ...
Страница 121: ...I L 40 385 5 A 49 I L 40 385 5 A 49 I L 40 385 5 A 49 Figure 38 Simplified MDAR Version 2 60 SPT Logic sub 4 1504B32 ...
Страница 122: ...I L 40 385 5 A 50 I L 40 385 5 A 50 I L 40 385 5 A 50 Figure 39 MDAR Block Diagram sub 1 1611C12 ...
Страница 123: ......
Страница 124: ......
Страница 125: ......