I.L. 40-385.5
5-2
current and voltage are updated once a cycle. The
values from the previous cycle are operated on while
the present cycle of data is being collected.
The Fourier coefficients and sums, as well as the
sum of squares of the inputs are calculated and
accumulated to provide RMS and phasor values of
current and voltage for distance measurement and
metering display. The RMS value of the ground cur-
rent is also needed for inverse-time ground protec-
tion.
Several functions are performed only in Background
Mode. The servicing of the operator interface is one
of these functions; the display is updated, pushbut-
tons are acknowledged, and the LED’s are con-
trolled. Metering of the analog inputs, updating the
target information for display purposes, and checking
the validity of the settings in the nonvolatile memory
are other functions performed only in Background
Mode.
Fault detection is in effect at all time in Background
Mode. Each sampled value of current and voltage is
compared to the sampled value from the previous
cycle. If the difference exceeds the established
threshold, a fault is suspected and Fault Mode is
entered. The zone-2 and zone-3 time delay distance
protection are performed in both Background Mode
and Fault Mode.
Содержание MDAR
Страница 84: ......
Страница 88: ...I L 40 385 5 A 16 Figure A 1 Test Connection for Single Phase to Ground Faults Sheet 1 of 4 1502B51 Sub 1 ...
Страница 89: ...I L 40 385 5 A 17 Figure A 2 Test Connection for Three Phase Faults 1502B51 Sub 1 Sheet 2 of 4 ...
Страница 90: ...I L 40 385 5 A 18 Figure A 3 Test Connection for Phase to Phase Faults 1502B51 Sub 1 Sheet 3 of 4 ...
Страница 96: ......
Страница 98: ...I L 40 385 5 A 26 I L 40 385 5 A 26 I L 40 385 5 A 26 Figure 5 MDAR REL 300 Relay Assembly sub 3 1502B21 ...
Страница 101: ......
Страница 102: ......
Страница 104: ......
Страница 105: ...I L 40 385 5 A 33 I L 40 385 5 A 33 I L 40 385 5 A 33 Figure 15 MDAR REL 300 Zone 1 Trip Logic sub 1 9659A66 ...
Страница 106: ...I L 40 385 5 A 34 I L 40 385 5 A 34 I L 40 385 5 A 34 Figure 16 MDAR REL 300 Zone 2 Trip Logic sub 1 9659A67 ...
Страница 107: ...I L 40 385 5 A 35 I L 40 385 5 A 35 I L 40 385 5 A 35 Figure 17 MDAR REL 300 Zone 3 Trip Logic sub 1 1504B04 ...
Страница 111: ......
Страница 112: ...I L 40 385 5 A 40 I L 40 385 5 A 40 I L 40 385 5 A 40 Figure 25 Load Loss Accelerated Trip Logic sub 2 1504B29 ...
Страница 116: ......
Страница 118: ...I L 40 385 5 A 46 I L 40 385 5 A 46 I L 40 385 5 A 46 Figure 35 Power Reversal sub 1 9654A17 ...
Страница 119: ...I L 40 385 5 A 47 I L 40 385 5 A 47 I L 40 385 5 A 47 Figure 36 Reverse Block Logic sub 1 9659A73 ...
Страница 120: ...I L 40 385 5 A 48 I L 40 385 5 A 48 I L 40 385 5 A 48 Figure 37 Unequal Pole Closing on Fault sub 1 9654A29 ...
Страница 121: ...I L 40 385 5 A 49 I L 40 385 5 A 49 I L 40 385 5 A 49 Figure 38 Simplified MDAR Version 2 60 SPT Logic sub 4 1504B32 ...
Страница 122: ...I L 40 385 5 A 50 I L 40 385 5 A 50 I L 40 385 5 A 50 Figure 39 MDAR Block Diagram sub 1 1611C12 ...
Страница 123: ......
Страница 124: ......
Страница 125: ......