I.L. 40-385.6
i
Significant Changes to Version 2.62 (From V2.60)
1.
Corrected the display for 1-a ct style. Now, the angles of currents will be blocked only if the magnitudes
of currents are below 10% of ct rating.
2.
Used JMP-3 to perform the following functions.
a) If JMP-3 = OUT, the 150 ms timer for LOPB maintains the same as V2.60, e.g., the LOPB will not block
the distance units if a fault is detected within 150 ms after LOP = 1.
b) If JMP-3 = IN, change the timer of 150 ms to 500 ms for the LOP condition.
3.
Removed LOPB and LOI from AL-1 relay and removed GS function. Use GS relay for LOPB or LOIB
alarm (AL-3).
4.
Corrected and removed KI0 from 3-phase fault formula for the distance protection and display.
5.
Added ITP/ITG to the Reclose logic. For V2.60 and 3ZNP application, MDAR may not give 3-pole reclos-
ing due to ITP/ITG trip if the zone-1 setting is “OUT”.
6.
Removed AND144C and OR144D. Used pre-fault voltages (FDOPA & FDOPB & FDOPC) to supervise
AND130 and AND176 for zone-1 and pilot high speed 3-phase fault trip, e.g., the pre-fault voltage super-
vision is always in regardless of the setting of OSB.
7.
Used TRSLA/TRSLB/TRSLC (OR54) to replace TRSL/HST at AND49A, AND49E and AND24 due to the
need of single pole application.
8.
Added AND144E between OR145 and OR144B for zone-1 and single pole trip. The AND144E has two
inputs - OR145 and X2. The relay should trip on the second fault after the SPT regardless of the phase
type selection.
9.
Added an OR76A between AND48A and AND76. Added WFT3 to the input of OR76A. In V2.60, there are
no trip actions for multi-phase fault (Ph-Ph or 3-Ph) with the settings of TTYP=SR3R, STYP=POTT and
WFEN=YES.
10.
Changed the SPF logic by removing the gates of OR77E, OR77F, OR77G, AND77A, OR77D. Added
gates AND48G and OR48H and a timer (2/0) between X2 and AND77. Version 2.60 did not show SPF
consistently and might not give RB signal.
11.
Added OR72A, OR73A, OR74A for single-pole phase-to-ground fault detection and AND48E, OR48F for
phase fault detection. This is for security purpose especially an evolving fault and/or high-set (ITG) trip
involved.
12.
TRSL (NOT) was added to the inputs of AND69, 70, 71 to prevent the SRI due to the pole-span alignment
during the three-pole clearing.
13.
Added XB (NOT) and XC (NOT) to AND72 for phase-A (similar changes for phase B, C on gates AND73,
74) to prevent 2-pole trip condition.
14.
LOIB timer was changed from 0.5/0.5 seconds to 10/0.5 seconds to insure the trip for zone-2 or zone-3
faults for the long time delay settings of T2 and T3.
15.
Corrected the software error to use the pre-fault voltage for the directional units (FDOG/RDOG) after sin-
gle-pole trip.
NOTE:
CONVERSION FROM MDAR FIRMWARE VERSION V2.60 TO V2.62 CAN BE ACCOMPLISHED
AS FOLLOWS:
Содержание MDAR
Страница 84: ......
Страница 88: ...I L 40 385 5 A 16 Figure A 1 Test Connection for Single Phase to Ground Faults Sheet 1 of 4 1502B51 Sub 1 ...
Страница 89: ...I L 40 385 5 A 17 Figure A 2 Test Connection for Three Phase Faults 1502B51 Sub 1 Sheet 2 of 4 ...
Страница 90: ...I L 40 385 5 A 18 Figure A 3 Test Connection for Phase to Phase Faults 1502B51 Sub 1 Sheet 3 of 4 ...
Страница 96: ......
Страница 98: ...I L 40 385 5 A 26 I L 40 385 5 A 26 I L 40 385 5 A 26 Figure 5 MDAR REL 300 Relay Assembly sub 3 1502B21 ...
Страница 101: ......
Страница 102: ......
Страница 104: ......
Страница 105: ...I L 40 385 5 A 33 I L 40 385 5 A 33 I L 40 385 5 A 33 Figure 15 MDAR REL 300 Zone 1 Trip Logic sub 1 9659A66 ...
Страница 106: ...I L 40 385 5 A 34 I L 40 385 5 A 34 I L 40 385 5 A 34 Figure 16 MDAR REL 300 Zone 2 Trip Logic sub 1 9659A67 ...
Страница 107: ...I L 40 385 5 A 35 I L 40 385 5 A 35 I L 40 385 5 A 35 Figure 17 MDAR REL 300 Zone 3 Trip Logic sub 1 1504B04 ...
Страница 111: ......
Страница 112: ...I L 40 385 5 A 40 I L 40 385 5 A 40 I L 40 385 5 A 40 Figure 25 Load Loss Accelerated Trip Logic sub 2 1504B29 ...
Страница 116: ......
Страница 118: ...I L 40 385 5 A 46 I L 40 385 5 A 46 I L 40 385 5 A 46 Figure 35 Power Reversal sub 1 9654A17 ...
Страница 119: ...I L 40 385 5 A 47 I L 40 385 5 A 47 I L 40 385 5 A 47 Figure 36 Reverse Block Logic sub 1 9659A73 ...
Страница 120: ...I L 40 385 5 A 48 I L 40 385 5 A 48 I L 40 385 5 A 48 Figure 37 Unequal Pole Closing on Fault sub 1 9654A29 ...
Страница 121: ...I L 40 385 5 A 49 I L 40 385 5 A 49 I L 40 385 5 A 49 Figure 38 Simplified MDAR Version 2 60 SPT Logic sub 4 1504B32 ...
Страница 122: ...I L 40 385 5 A 50 I L 40 385 5 A 50 I L 40 385 5 A 50 Figure 39 MDAR Block Diagram sub 1 1611C12 ...
Страница 123: ......
Страница 124: ......
Страница 125: ......