DEFAULT DATA MAP
DATA MAPPING
64
1TGC908004
Hardware-Local overrides all other CA Levels. It is not possible for the DCS or MView to take
control when the M10x is set to HW-Local.
Recommended procedure for sending control commands for a motor starter
1.
Set the M10x to "Remote" with the command “0x2100”
2.
2.Set the desired state, "Run Reverse", "Off", "Run Forward" or "Trip Reset"
3.
Wait until desired state is shown in motor state (received from Slave).
4.
Reset previous command "Run Reverse", "Off", "Run Forward" or "Trip Reset"