CONFIGURATIONS
SETTINGS – DCS MODBUS RTU
COMMUNICATION
1TGC908004
39
Figure 32 Parameter Window for Serial Switchgear Bus in MNavigate
7.4.
Settings – DCS Modbus RTU Communication
These settings are only applicable if the communication to DCS is Modbus RTU (Serial 2 port
at Digital Gateway).
Parameter
Default Value
Range
Remarks
Slave address 1
247
1…247
RTU Slave Address
Slave address 2
0
1…247
Only for MNS Digital Upgrade
solution for INSUM 1:
Slave address 1 define device
number 1 to 32, slave address 2 de-
fine device number 33 to 64
Baud rate
19200
9600,
19200,
38400,
115200
Data Transmission Speed
Parity bit
Even
None,
Even, Odd
Used for Error checking
Stop bit
1
1 or 2
Required if no Parity check is used
PLC Time Out enable
No
Yes / No
Activates PLC time out