manualshive.com logo in svg
background image

 

2105824-001 rev. AA

 | 9

 

4.  Remove the wires from the connector(s). If two connectors were removed, keep 

for rewire. 

5.  Hold the existing board by the edges, and pull it out slowly. 
6.  Unplug the 16-pin connector at the bottom of the board to detach the board from 

the sensor assembly inside the casing. 

7.  Place the removed board in a safe place (protect from static 

electricity).Connection to the board is required to obtain configuration. 

8.  Unscrew the conduit to detach from enclosure. Leave wire ends hanging. 
9.  Replace the cover on the electronics enclosure. 
10.  Loosen the nut on the cord connector. 

 

IMPORTANT NOTE:

 There should be no cord connector on high 

pressure units. 

11.  Unscrew the tank port bushing. 
12.  Remove the LevelMaster from the tank and lay it on the ground using the 

wooden blocks underneath for support (If no wooden blocks are available use 
any stable and even support to keep the unit from rotating while in horizontal 
position). 

13.  Proceed to replace the existing floats. 

4.2  Replace the existing floats 

To replace existing floats: 
1.  Remove the float clamp from the bottom of the casing. 
2.  Slide the float(s)

 

off the bottom of the casing. 

3.  Slide the new float(s) onto the bottom of the casing. If using two floats, install in 

the correct order (Figure 3). 

 

IMPORTANT NOTE:

 Position the float(s) correctly so that the text on 

the float label would be in the upright position when the LevelMaster is 
inserted back into the tank. 

a.  Install the oil level float first. 
b.  Install the water level float second. 

OIL

 

FL

OAT

WAT

E

FL

OAT

1

2

TOP OF 

LEVELMASTER

 

Figure 3: Positioning the floats for dual float configuration 

4.  Slide the float clamp back onto the bottom of the casing. 
5.  Use a Phillips screwdriver to tighten the clamp 1 inch above the bottom of the 

casing. Considerable force may be required to lock the clamp on tight. 

Содержание LevelMaster 7100

Страница 1: ...g IMPORTANT NOTE This guide does not address any requirements for the removal or installation of product s in hazardous classified locations Refer to the installation instructions and local and nation...

Страница 2: ...xperiencing issues downloading the software call a local ABB representative or call the main office number listed on the back page of this guide Assumptions The following apply to this guide The Level...

Страница 3: ...signal word CAUTION indicates a potentially dangerous situation Failure to observe this safety information may result in property damage The symbol may also be used for minor injury warnings The text...

Страница 4: ...contents are inspected and found to be free of damage CAUTION Equipment damage A static electric discharge can result in damage to the electronic board Wear a grounding strap to eliminate static elec...

Страница 5: ...aging all the installed LevelMasters with MasterLink 2 0 configuration files may be copied to the new installation directory To install 1 Go to the Liquid level sensor LCM7100 page click the Downloads...

Страница 6: ...to perform the upgrade Tools and material Phillips screwdriver Small slotted screwdriver 24 inch pipe wrench Wooden blocks or other means to support the sensor on the floor when removed from the tank...

Страница 7: ...e communication port RS485 to RS232 Converter cable 2100241 002 Contains 2 batteries 9 Vdc Both boards RS232 to USB converter cable Third party manufacturer Use if connecting to a USB port on a laptop...

Страница 8: ...ensor calibration data Figure 2 shows the top of an installed LevelMaster Use as a reference for this procedure TANK PORT BUSHING CORD CONNECTOR TANK ELECTRONICS ENCLOSURE NUT Figure 2 Top of the Leve...

Страница 9: ...If no wooden blocks are available use any stable and even support to keep the unit from rotating while in horizontal position 13 Proceed to replace the existing floats 4 2 Replace the existing floats...

Страница 10: ...Select the laptop communication port used 5 Leave Baud Rate at 9600 It assumed the board was at the default baud rate If not set at the default rate select the other option 1200 6 Click Setup LevelMas...

Страница 11: ...sion IMPORTANT NOTE The default path for the saved file depends on the MasterLink version used The files are automatically saved in the main installation directory of each version Make sure to take no...

Страница 12: ...and forefinger making sure the apex of the arch is placed against the board while the ends of the tab are braced to the inside of the housing 7 Proceed to configure the board 4 5 Configure the new boa...

Страница 13: ...2 Configure the new electronic board with the existing configuration Use this procedure if configuring the new board with the existing configuration file saved in section 4 3 3 Save the configuration...

Страница 14: ...default configuration Use this procedure if configuring the new board with one of the default files included with the MasterLink software Using the default file provides only calibration data for the...

Страница 15: ...AA 15 Figure 7 Downloading correct configuration to the LevelMaster 6 Click Download Data to LevelMaster 7 Click OK when the download is complete 8 Click the Setup tab Figure 8 Figure 8 Configure the...

Страница 16: ...shing communication 11 From the monitor screen verify that the level and temperature readings display expected values based on the float position and temperature See section 4 6 Verify measurements 12...

Страница 17: ...nd New Value 8 Verify that the RS485 termination address is now set to 1 Figure 11 Figure 11 RS485 termination for the last sensor IMPORTANT NOTE The RS485 bus termination value for intermediate Level...

Страница 18: ...ndicate the position of the float s 3 Slide the floats to several positions on the sensor and verify that the screen updates and reflects the correct level for the floats 4 Proceed to ground the unit...

Страница 19: ...r conduit into the electronics enclosure for the communications and power wiring 7 Proceed to restore the field wiring next 4 9 Restore field wiring The new electronic headboard has two separate ports...

Страница 20: ...ource if unable to power the unit from the flow computer or controller 3 Insert the wires in the power connector observing correct polarity Figure 14 a Connect to flow computer remote controller COM p...

Страница 21: ...bus wire as shown in Figure 16 Figure 17 page 22 or Figure 18 page 22 IMPORTANT NOTE Review the Phoenix Contact terminal connection specifications for acceptable wire gauge and type when connecting m...

Страница 22: ...smits signals on the communication port If these LEDs do not lit up check the wiring 4 10 Verify installation using PCCU If the LevelMaster is connected to an ABB Totalflow flow computer or remote con...

Страница 23: ...r counts should display Figure 19 Figure 19 Verify sensor measurements from PCCU 5 Verify that the temperature measurement is the expected value It must reflect the temperature in the tank 6 Verify th...

Страница 24: ...ling Verify converter cable and adaptors are securely attached Verify batteries on converter cable are charged and connected correctly positive voltage terminal must be connected to red wire Install d...

Страница 25: ...es 5 2 2 Measurement errors displayed by the LevelMaster application The errors described in Table 6 display on the LevelMaster Tank number tab If multiple tanks are configured under the LevelMaster a...

Страница 26: ...26 2105824 001 rev AA Figure 20 Measurement errors...

Страница 27: ...2105824 001 rev AA 27 Notes...

Страница 28: ...ginal US English version of this manual shall be deemed the only valid version Translated versions in any other language shall be maintained as accurately as possible Should any discrepancies exist th...

Отзывы: