Addr.
(hex)
Addr.
(dec)
Word
(16-bit)
Slave
Modbus
ID
Category
Description
Unit Format
Access EQ Meter
Resolution
M4M
Res.
M2M
Res.
94E1
38113
4
1
Other
Reset counter
(resettable active
energy export)
-
Unsigned
R
1
1
-
94E5
38117
4
1
Other
Reset counter
(resettable
reactive energy
import)
-
Unsigned
R
1
1
-
94E9 38121
4
1
Other
Reset counter
(resettable
reactive energy
export)
-
Unsigned
R
1
1
-
94ED 38125
3
1
Other
Date Time
YYMMDD:HHMMSS
-
Unsigned
R/W
1
1
-
94F0 38128
2
1
Other
CURRENT
THRESHOLD
for TIMER-2
ACTIVATION
mA
Unsigned
long
R
-
-
1
94F2
38130 2
1
Other
PULSE ENERGY
WEIGHT
-
Unsigned
long
R/W
-
-
1
94F4 38132
1
1
Other
Day of week
-
Unsigned
R
1
1
-
94F5
38133
1
1
Other
DST active
-
Unsigned
R
1
1
-
94F6 38134 1
1
Other
Active day type
-
Unsigned
R
1
1
-
94F7
38135
1
1
Other
Active season
-
Unsigned
R
1
1
-
Device information
Addr.
(hex)
Addr.
(dec)
Word
(16-bit)
Slave
Modbus
ID
Category
Description
Unit Format
Access EQ Meter
Resolution
M4M
Res.
M2M
Res.
94F8 38136 8
1
Production
data
Meter firmware
version
text
String
R
1
1
-
9500 38144 8
1
Production
data
Slave ID
-
Unsigned
R
-
1
-
9508 38152 8
1
Production
data
Logical device
name
text
String
R
-
1
-
9510 38160 6
1
Production
data
Type
designation
text
String
R
1
1
-
9516 38166 5
1
Production
data
Serial
number(s)
-
Unsigned
R
1
1
-
951B 38171 1
1
Production
data
Modbus
mapping
version
-
Unsigned
R
1
1
-
Device settings
Addr.
(hex)
Addr.
(dec)
Word
(16-bit)
Slave
Modbus
ID
Category
Description
Unit Format
Access EQ Meter
Resolution
M4M
Res.
M2M
Res.
951C
38172
2
1
Settings
1st reg: Actions,
2nd reg: output
nr On/Off delay
-
Unsigned
R/W
-
1
-
951E
38174
4
1
Settings
Complex Alarms
Components
-
Unsigned
R/W
-
1
-
9522
38178
3
1
Settings
I/O settings (incl
pulse outputs)
Energy quantity
OBIS code
-
Unsigned
R/W
1
1
1
9525
38181
3
1
Settings
Load profile
settings Quantity
OBIS code
-
Unsigned
R/W
-
1
-
9528
38184 3
1
Settings
Demand settings
Channel quantity
OBIS code
-
Unsigned
R/W
-
1
-
952B
38187
3
1
Settings
Demand settings
Level quantity
OBIS code
-
Unsigned
R/W
-
1
-
952E
38190 3
1
Settings
Alarm settings
Quantity OBIS
-
Unsigned
R/W
-
1
-
88
SCU100
INSITE PRO M COMPACT USER MANUAL
Содержание INSITE PRO M COMPACT SCU100
Страница 1: ...INSITE PRO M COMPACT SCU100 User manual SCU100 User manual ...