Modbus Standard TCP Port: 8001
Standard SNMP Port:
8002
Addr.
(hex)
Addr.
(dec)
Word
(16-bit)
Description
Resolution
(1-bit value)
Unit
Format
Access SNMP
Variable Name
Ongoing measurement values:
These registers contain the actual measured data.
0000
0
1
TRMS value of Sensor 1
0.01
A
unsigned
R (03)
TRMSsens1
0001
1
1
TRMS value of Sensor 2
0.01
A
unsigned
R (03)
TRMSsens2
…
…
1
…
0.01
A
unsigned
R (03)
…
005F
95
1
TRMS value of Sensor 96
0.01
A
unsigned
R (03)
TRMSsens96
0100
256
1
AC value of Sensor 1
0.01
A
unsigned
R (03)
ACsens1
0101
257
1
AC value of Sensor 2
0.01
A
unsigned
R (03)
ACsens2
…
…
1
…
0.01
A
unsigned
R (03)
…
005F
351
1
AC value of Sensor 96
0.01
A
unsigned
R (03)
ACsens96
0200
512
1
DC value of Sensor 1
0.01
A
signed
R (03)
DCsens1
0201
513
1
DC value of Sensor 2
0.01
A
signed
R (03)
DCsens2
…
…
1
…
0.01
A
signed
R (03)
…
025F
607
1
DC value of Sensor 96
0.01
A
signed
R (03)
DCsens96
Minimum measured values:
These registers contain the minimum measured values since last system start / reset or since last “reset min/max
values” request.
0400
1'024 1
TRMS min value of Sensor 1 0.01
A
unsigned
R (03)
MINTRMSsens1
0401
1'025 1
TRMS min value of Sensor 2 0.01
A
unsigned
R (03)
MINTRMSsens2
…
…
1
…
0.01
A
unsigned
R (03)
…
045F
1'119
1
TRMS min value of Sensor
96
0.01
A
unsigned
R (03)
MINTRMSsens96
0500
1'280 1
AC min value of Sensor 1
0.01
A
unsigned
R (03)
MINACsens1
0501
1'281
1
AC min value of Sensor 2
0.01
A
unsigned
R (03)
MINACsens2
…
…
1
…
0.01
A
unsigned
R (03)
…
055F
1'375 1
AC min value of Sensor 96
0.01
A
unsigned
R (03)
MINACsens96
0600
1'536 1
DC min value of Sensor 1
0.01
A
signed
R (03)
MINDCsens1
0601
1'537 1
DC min value of Sensor 2
0.01
A
signed
R (03)
MINDCsens2
…
…
1
…
0.01
A
signed
R (03)
…
065F
1'631
1
DC min value of Sensor 96
0.01
A
signed
R (03)
MINDCsens96
Maximum measured values:
These registers contain the maximum measured values since last system start / reset or since last “reset min/max
values” request.
0800
2'048 1
TRMS max value of Sensor
1
0.01
A
unsigned
R (03)
MAXTRMSsens1
0801
2'049 1
TRMS max value of Sensor
2
0.01
A
unsigned
R (03)
MAXTRMSsens2
…
…
1
…
0.01
A
unsigned
R (03)
…
085F
2'143 1
TRMS max value of Sensor
96
0.01
A
unsigned
R (03)
MAXTRMSsens96
0900
2'304 1
AC max value of Sensor 1
0.01
A
unsigned
R (03)
MAXACsens1
0901
2'305 1
AC max value of Sensor 2
0.01
A
unsigned
R (03)
MAXACsens2
…
1
…
0.01
A
unsigned
R (03)
…
095F
2'399 1
AC max value of Sensor 96
0.01
A
unsigned
R (03)
MAXACsens96
0A00
2'560 1
DC max value of Sensor 1
0.01
A
signed
R (03)
MAXDCsens1
0A01
2'561 1
DC max value of Sensor 2
0.01
A
signed
R (03)
MAXDCsens2
…
…
1
…
0.01
A
signed
R (03)
…
0A5F
2'655 1
DC max value of Sensor 96 0.01
A
signed
R (03)
MAXDCsens96
76
SCU100
INSITE PRO M COMPACT USER MANUAL
Содержание INSITE PRO M COMPACT SCU100
Страница 1: ...INSITE PRO M COMPACT SCU100 User manual SCU100 User manual ...
Страница 2: ......
Страница 93: ...Note SCU100 INSITE PRO M COMPACT USER MANUAL 93 ...
Страница 94: ...Note 94 SCU100 INSITE PRO M COMPACT USER MANUAL ...
Страница 95: ......
Страница 96: ...ABB S p A Electrification business Viale dell Industria 18 20010 Vittuone MI Italy new abb com low voltage ...