4.Technical characteristics / specifications
4.1.Overall dimensions and technical data sub-distribution control unit
87
162
64,2
IEC61010-1
Supply voltage
[VAC]
90-240 (L1-N)
Voltage measurement range
[VAC]
90-240 (L1-N, L2-N, L3-N)
UL 508 / CSA C22.2 No. 14
Supply voltage
[VAC]
80-277 (L1-N)
Voltage measurement range
[VAC]
80-277 (L1-N, L2-N, L3-N)
General
Frequency
[Hz]
50 / 60
Power consumption (L1-N)
[VA]
5 .. 45
(depending on number of sensors and I/O modules)
Current measurement range
Current transformer
(secondary wire of CT)
[A]
nominal: 5
max.: 6
Data refresh time
1sec / 30 sec (depending on type of data)
Operating temperature
[°C]
-25 .. +60
Storage temperature
[°C]
-40 .. +85
LAN (RJ45 connector)
[Mbit/s] 100
Modbus RTU
[Baud]
RS485 2-wire, 2400..115200
Cable cross section*
1.0.. 2.5 mm²
(max. 0.8 Nm)
Stripping length
[mm]
10
Tightening torque of screws
[Nm]
0.5..0.8
Mounting DIN-rail
35 mm DIN50022
Dimensions
[mm]
160.0 x 87.0 x 64.9 (9 DIN modules)
Overvoltage category
II
Pollution degree
2
Altitude
[m]
2000
Safety class
IP20
Main circuit accuracy
Voltage
± 1 %
Current
± 1 %
Harmonic component (up to 2500Hz)
± 1 %
Active power
± 2 %
Apparent power
± 2 %
Reactive power
± 2 %
Power factor
± 2 %
Standards
Electrical safety
IEC 61010-1
EMC
IEC 61326-1
*Line protection is recommended (acc. IEC61439) min. 6A, max 8A for 1mm2, 12A for 1.5mm2, 20A for 2.5mm2.
Do not operate the equipment outside the specified technical data and not intended use.
16
SCU100
INSITE PRO M COMPACT USER MANUAL
Содержание INSITE PRO M COMPACT SCU100
Страница 1: ...INSITE PRO M COMPACT SCU100 User manual SCU100 User manual ...
Страница 2: ......
Страница 93: ...Note SCU100 INSITE PRO M COMPACT USER MANUAL 93 ...
Страница 94: ...Note 94 SCU100 INSITE PRO M COMPACT USER MANUAL ...
Страница 95: ......
Страница 96: ...ABB S p A Electrification business Viale dell Industria 18 20010 Vittuone MI Italy new abb com low voltage ...