Troubleshooting
To minimize potential sources of error, there are certain principles you should follow:
Installation:
•
Check cable length, polarity, termination resistors, etc.
Configuration:
•
The server manual is available.
•
The baud rate and parity must be the same for all the devices in the Modbus system.
•
Each Modbus server is assigned a unique address.
•
Server data points (function codes, register numbers, format, etc.) are correctly entered in the
gateway in accordance with the server specification.
•
General server information such as processing times were taken into account in the gateway
configuration.
There are Modbus tools for simulating and testing the communication between client and server. Example:
https://www.modbustools.com/index.html
Other support tools, e.g. Engineering Guides, FAQs, etc. are available on our website