ABB i-bus
®
KNX
Commissioning
AA/S 4.1.2, AA/A 2.1.2 | 2CDC505163D0201 55
3.3.3
Output objects
3.3.3.1
Group objects General
No.
Function
Object name
Data type
Flags
1
In operation
General
1 bit
DPT 1.002
C, R, T
This group object is enabled if the parameter
Enable group object "In operation", 1 bit
is set to
Yes
and the dependent parameter
Send
is set to
Value 0
or
Value 1
.
In order to regularly monitor the presence of the device on the ABB i-bus
®
KNX, a telegram In operation can be sent
cyclically on the bus. As long as the group object is activated, it sends a telegram In operation.
Telegram value:
1 = Send system in operation with option
Value 1
0 = Send system in operation with option
Value 0
2
Status Auxiliary voltage
(not applicable to AA/A 2.1.2)
General
1 bit
DPT 1.002
C, R, T
This group object is enabled if the parameter
Enable group object "Status Auxiliary voltage" 1 bit
Yes
.
Telegram value:
0 = Auxiliary voltage failure, all outputs = 0 V/mA
1 = Auxiliary voltage is active
3
Status byte channel A/B
General
Non DPT
C, R, T
The status byte reflects the current status of channel A/B.
Different statuses are indicated here, e.g.
Status Channel A
– forced operation active
Status Channel B
– fault at output
Bit
sequence:
76543210
Bit 7:
Not assigned
Always 0
Bit 6:
Not assigned
Always 0
Bit 5:
Channel A: Forced operation
0: Forced operation is not active (channel A)
1: Forced operation is active (channel A)
Bit 4:
Channel A: Cyclical monitoring
0: Cyclical monitoring is not active (channel A)
1: Cyclical monitoring is active (channel A)
Bit 3:
Channel A: Fault at output
0: No fault at output (channel A)
1: Fault at output (channel A)
Bit 2:
Channel B: Forced operation
0: Forced operation is not active (channel B)
1: Forced operation is active (channel B)
Bit 1:
Channel B: Cyclical monitoring
0: Cyclical monitoring is not active (channel B)
1: Cyclical monitoring is active (channel B)
Bit 0:
Channel B: Fault at output
0: No fault at output (channel B)
1: Fault at output (channel B)
For further information see:
Value table of group object Status byte channel A/B
Содержание i-bus KNX AA/A 2.1.2
Страница 1: ...ABB i bus KNX Analogue Actuator AA S 4 1 2 AA A 2 1 2 Product Manual ...
Страница 2: ......
Страница 4: ......
Страница 20: ......
Страница 51: ...ABB i bus KNX Commissioning AA S 4 1 2 AA A 2 1 2 2CDC505163D0201 49 Priorities ...
Страница 65: ...ABB i bus KNX Appendix AA S 4 1 2 AA A 2 1 2 2CDC505163D0201 63 Notes ...
Страница 66: ...ABB i bus KNX Appendix 64 2CDC505163D0201 AA S 4 1 2 AA A 2 1 2 Notes ...
Страница 67: ......