– Make sure that the insulating parts of the
switchgear are not damaged when the
apparatus is handled.
– Before proceeding with any operation, always
make sure that the springs of the operating
mechanism are discharged and that the
switchgear is on the ground.
– Keep the switchgear in the horizontal position
when it is handled.
3. Storage
The switchgear must be stored in a dry, dust-free, non-
corrosive place at a temperature between – 5 °C and 45
°C for the standard version and between – 40 °C e + 45 °C
for the low temperature version. Please consult us if special
requirements are involved.
The switch-disconnectors will have been strapped to the
wooden pallet. Cut the strap to unload the equipment.
For handling purposes, the switch-disconnector can be lifted
by a crane fitted with ropes and snap hooks conforming to
the safety standards, to be fastened to the two anchor points
provided. The switch-disconnector can also be shifted by
hand. In this case, lift it by the operating mechanism part on
one side and from the eyebolts (1) on the other side. Switch-
disconnectors weigh approximately 75 kg.
Fig. 1
4. Handling