5.4. Construction characteristics
5.4.1. Switch-disconnectors
GSec is a three-position switch-disconnector (line-open-
earthed). The enclosure of the GSec switch-disconnector
consists of two half-shells, the top part being made of resin
and the bottom part in stainless steel.
GSec apparatus is “sealed for life” in accordance with
standard IEC 62271, i.e. gas tightness is guaranteed for over
30 years.
Insulating bushings are fixed to the disconnector enclosure:
three upper ones for connecting the busbars housed in the
busbar compartment (upper) and three lower ones for the
line compartment applications (cables and terminals, fuses,
earthing switch and instrument transformers).
5.4.2 Protection classes
The GSec switch-disconnector is designed according to the
following protection classes:
SF6 enclosure:
IP65
Front operating mechanism
(with cover assembly 2RDA017777):
IP2X (excluding lever seats)
Switch-disconnector
The switch-disconnector (fig. 8) is the three-position IMS type.
Thus the moving contacts can set to three positions:
1) IMS closed
2) IMS and ST open
3) ST closed.
The following types of GSec apparatus can be supplied.
GSec/T1:
three-position switch-disconnector with manual
operation once dead-center has been passed. It is normally
used to make incoming/outgoing compartments.
GSec/T2:
three-position switch disconnector with manual and
stored energy operating mechanism.
It is normally used to make incoming/outgoing compartments
and can be equipped with shunt opening release.
GSec/T2F:
three-position switch disconnector with manual
and stored energy operating mechanism, fuse holder frame,
tripping device in case of blown fuses, earthing switch on
load side of fuse holder frame. It is normally used to make
transformer protection compartments and can be equipped
with shunt opening release.
GSec/IB:
three-position line-side isolator with manual
operation once dead-center has been passed and spaced
earthing switch, interlocked with the earthing switch of
the IMS. It is normally used to make incoming/outgoing
compartments with fixed circuit-breakers.
– Do not drill or weld the stainless steel
enclosure of the apparatus.
– The copper connections must be assembled
on the insulators using a torque wrench and
33 Nm tightening torque.
5.4.3. Main components
IMS
Operating
mechanism
Earthing switch
GSec/T1
1S
ST
GSec/T2
2S
ST
GSec/T2F
2S
ST2 - EF 230
GSec/IB
1S
ST1 - ES 230