31
6.5. Replacing and installing new
apparatus
6.5.1. Replacing tripped fuses
Troubleshooting and cleaning
The fuses cannot be regenerated. According to IEC
Publication 60282-1, all three fuses must be replaced even
if only one or two of them have blown. Exceptions are
allowed when verifications have found that the fuses have
not been subjected to any overcurrent. If the fused switch-
disconnector units (T2F) are equipped with a fuse tripping
mechanism, the switch-disconnector opens automatically
by means of the striker pin/s of the fuse/s and the tripping
mechanism.
Fig. 53 - Position indicator
Fig. 54 - Fuses installed
Fig. 55 - Fuses disassembled
Instructions
− Check that the colour of the fuse indicator is red and that
the position indicator is in the “open” position.
− Turn the switch to the “earthed” position (see chapter 5.12.
Switch-disconnector operating instructions.
− Open the door.
− The upper and lower fuse holders are earthed and the fuses
can be removed and installed by hand.
Removing the fuses
a) Start from phase L1 (near the door).
b) Pull the fuse by its upper part until it has been released.
c) Lift the fuse upwards so that the lower part is also
released.
d) Repeat this procedure for phases L2 and L3.