5 Electrical Interconnections Converter
D184B122U02
S4
17
5.6
Interconnection Diagram: Older Flowmeter Primary DN 3–1000 [1/10”–40”],
Converter Field Mount Housing Model 10D1422
(10DI1425, 10DS3111A-C DN 500–1000 [20”– 40”])
Fig. 8:
Interconnection Diagram Converter S4 Older Flowmeter Primaries
Comment:
We recommend that shielded output cables be used with the shields connected to earth at one end.
!
Attention!
Check supply voltage and flowmeter primary, see type tag on flowmeter primary.
On the connection board in the converter the hook switch S903 must be closed. See
Pages 55 and 60.
1)
Supply Power
High voltage:
Frequency:
AC 85–253V
Terminals L, N,
47 Hz
≤
f
≤
53 Hz; 50 Hz Supply Power
56 Hz
≤
f
≤
64 Hz, 60 Hz Supply Power
2)
Magnet Coil Supply:
Magnet Coil Supply from Supply Power
3) – 6) Output Cables
see Page 18
7)
Shielded Signal Cable:
Use ABB Part No. D173D018U02 or incorporate into the existing wiring.
8)
Reference Cable:
Only for connection to Model 10D1422
Reference Cable to Terminals: 6,7
L
M3 M1
32
31
51 52
41
N
1)
2)
3)
4)
82
1
2S
2
16
1S
3
8)
42
6)
7)
3
6
7
SE
L
N
6
7
3
81
24 V
+
-
5)
1
2
Earth
Earth
Converter S4
Wall Mount Housing
Flowmeter Primary
Connection board: D685A1020U03