6.2.9. Jumper
The position of the jumpers should only be read
after disconnecting the power supply with a
complete discharge of capacitors. Setting the
jumper position is only possible with the power
supply disconnected and capacitors completely
discharged.
6.2.9.1. JP1001 –Standard Open / Protection Trip
Setting of BI Y4 to “Standard Open” or “Protection
trip” input
6.2.9.2. JP1019 – EnergY CONSUMPTION
By setting this jumper, the power consumption is
reduced during the capacitor charging time. As a
result, the charging time is extended accordingly.
PRODUCT FAMILY: FSK II +
- OPERATING AND MAINTENANCE MANUAL
20
PRODUCT FAMILY: FSK II +
- OPERATING AND MAINTENANCE MANUAL
20
1V
S
R
6
3
0
2
0
6
E
N – e
n – E
D
O
-D
0
0
0
2
8
5
2
– I
n
st
ru
ct
io
n m
an
u
al – 2
0
21
.1
0 D
es
ig
n a
n
d s
p
ec
if
ic
at
io
n a
re s
u
b
je
ct t
o c
h
an
g
e w
it
h
o
ut n
o
ti
ce
—
6. Technical Data
DANGER!
IMPORTANT!
Jumper JP1001
Function
1 2 3
Input active as protection trip
Input active as standard open
Table 13 Jumper 1001
Jumper JP1019
Function
OFF
Standard energy consumption
~75W
ON
Reduced energy consumption
~33W
Table 14 Jumper 1019
Example of Jumper
Position 2-3
6.3. Weights and Dimensions
The weight specifications refer to the apparatus /
accessories and do not include any specifications
for packaging.
6.5. Torques for tightening screws
and nuts
Torques described in the table below are to be
applied with a suitable torque spanner.
For the screw sizes M6 to M16, the tightening
torque corresponds to screws with a strength
quality of 8.8 and an achieved permissible
tensioning of 90% of the yield point Rp0.2.
6.6. Interfaces
6.6.1. Mechanical/Electrical
The general definition of the interfaces can be
taken from the associated, applicable dimensional
drawing and can vary from project to project. This
applies to the fastening holes and screws of the
pole, the control box and to the layout of the main
and auxiliary power connections.
6.6.2. Earthing Connections
The exact earthing positions of the apparatus can
be taken from the associated, applicable
dimensional drawing.
The earthing connection is to be carried out with
the M12 screws/ stud.
6.4. Operating Conditions
Designation
Weight [kg]
Outside Dimensions
W*D*H [mm]
Apparatus FSK 1025
120
1
) .-… 150
2
)
320 x 320 x 1900
Small Control box
3
)
25
400 x 320 x 440
Large Control box
3
)
50
550 x 330 x 800
Table 15 Approx. values
1
) for silicon insulators
2
) for ceramic insulators
3
) without mounting profiles
Designation
Value
Operating environment temperature
-25 °C.. +40 °C
Altitude
< 1000m
Pressure
600 … 1100mbar abs.
Table 16 Standard operation conditions
Thread Size
Nominal Tightening Torque [Nm]
M4
3
M5
5.9
M6
10.1
M8
24.6
M10
48
M12
84
M16
110
Table 17 Screw tightening torques (screws are
lubricated)