6.1.2. Circuit breaker FSK1025
Designation
Value
Type: 2500
Frequency
50 Hz -60Hz
Operating voltage
25 kV
Number of phase
1 or 2
Rated voltage
acc. To EN 50124-1
27.5 kV
acc. To EN 60694
27.5 kV
Rated power frequency withstand voltage
(50Hz / 1 min)
Phase to earth
105 kV
Across open contacts
105 kV
Electromagnet, electronics and wiring to earth
2 kV
Rated lightning impulse withstand voltage
(1.2/50
µ
s)
Phase to earth
250 kV
Across open contacts
250 kV
Rated currents
Normal current
≤2500 A
Short-circuit breaking current
25 kA
Rated peak withstand current
63 kA
Short circuit making current
63 kA
Short time withstand current (3 s)
25 kA
Rated operating sequence
CB
O – 0.3s – CO – 60s – CO
Closing time
≤ 65 ms
Opening time
≤ 45 ms
Strength of the circuit breaker pole
Operating cycles
- mechanical
class M2=
10000
- with maintenance
30000
Strength of the vacuum interrupter
Mechanical operating cycles
20000
Electric power at rated current
20000
Electric power at rated short-circuit break current
50