6.2.8.3. I1004 Delay Time for Undervoltage-Trip
6.2.8.4. I1004 Operating Mode LOCAL/GLOBAL/REMOTE
6.2.8.5. I1004 Behaviour under Energy failure conditions (capacitor voltage)
Dip Switch I1004
Delay Time tdelay
1 2 3 4 5
ON
OFF
X
X
X
Undervoltage-trip function inactive
ON
X
OFF
X
X
20 ms
ON
X
OFF
X
X
0.5 s
ON
X
X
OFF
X
1 s
ON
X
OFF
X
X
2 s
ON
X
X
OFF
X
3 s
ON
X
X
OFF
X
4 s
ON
X
X
X
OFF
5 s
Table 10 Dip Switches I1004-2/3/4
Dip Switch I1004
Function
1 2 3 4 5
ON
X
OFF
LOCAL/GLOBAL
ON
OFF
X
LOCAL/REMOTE
Table 11 Dip Switch I1004-5
Dip Switch I1004
Function
1 2 3 4 5
ON
X
OFF
Energy failure autotrip, active
ON
OFF
X
Energy failure autotrip, inactive
Table 12 Dip Switch I1004-1