![background image](http://html1.mh-extra.com/html/abb/fsca-01/fsca-01_manual_3339443031.webp)
Communication profiles
31
5
RAMP_HOLD
1
Enable ramp function.
Proceed to
RAMP FUNCTION GENERATOR:
ACCELERATOR ENABLED
.
0
Halt ramping (Ramp Function Generator output
held).
6
RAMP_IN_
ZERO
1
Normal operation. Proceed to
OPERATING
.
Note:
This bit is effective only if the fieldbus interface
is set as the source for this signal by drive
parameters.
0
Force Ramp Function Generator input to zero.
7
RESET
0=>1 Fault reset if an active fault exists. Proceed to
SWITCH-ON INHIBITED
.
Note:
This bit is effective only if the fieldbus interface
is set as the source for this signal by drive
parameters.
0
Continue normal operation.
8 to 9 Reserved.
10
REMOTE_
CMD
1
Fieldbus control enabled.
0
Control Word <> 0 or Reference <> 0: Retain last
Control Word and Reference.
Control Word = 0 and Reference = 0: Fieldbus
control enabled. Reference and deceleration/
acceleration ramp are locked.
11
EXT_CTRL_
LOC
1
Select External Control Location EXT2. Effective if
control location parameterised to be selected from
fieldbus.
0
Select External Control Location EXT1. Effective if
control location parameterised to be selected from
fieldbus.
12 to
15
Drive-specific (For information, see the drive documentation.)
Bit
Name
Value
STATE/Description
Содержание FSCA-01
Страница 1: ...ABB Drives Modbus Protocol Manual RS 485 Adapter Module FSCA 01...
Страница 2: ......
Страница 4: ......
Страница 6: ...Safety instructions 6...
Страница 22: ...Drive configuration 22...
Страница 24: ...Master configuration 24...
Страница 46: ...Communication 46...
Страница 50: ...Definitions 50...
Страница 51: ......