Communication profiles
30
Table 7. The Control Word for the ABB Drives communication
profile. The upper case boldface text refers to the states shown in
Figure
Bit
Name
Value
STATE/Description
0
OFF1_
CONTROL
1
Proceed to
READY TO OPERATE
.
0
Stop along currently active deceleration ramp.
Proceed to
OFF1 ACTIVE
; proceed to
READY TO
SWITCH ON
unless other interlocks (OFF2, OFF3)
are active.
1
OFF2_
CONTROL
1
Continue operation (OFF2 inactive).
0
Emergency OFF, coast to stop.
Proceed to
OFF2 ACTIVE
, proceed to
SWITCH-ON
INHIBITED
.
2
OFF3_
CONTROL
1
Continue operation (OFF3 inactive).
0
Emergency stop, stop within time defined by drive
parameter. Proceed to
OFF3 ACTIVE
; proceed to
SWITCH-ON INHIBITED
.
Warning:
Ensure motor and driven machine can be
stopped using this stop mode.
3
INHIBIT_
OPERATION
1
Proceed to
OPERATION ENABLED
.
Note:
Run enable signal must be active; see the
drive documentation. If the drive is set to receive the
Run enable signal from the fieldbus, this bit activates
the signal.
0
Inhibit operation. Proceed to
OPERATION
INHIBITED
.
4
RAMP_OUT_
ZERO
1
Normal operation. Proceed to
RAMP FUNCTION
GENERATOR: OUTPUT ENABLED
.
0
Force Ramp Function Generator output to zero.
Drive ramps to stop (current and DC voltage limits in
force).
Содержание FSCA-01
Страница 1: ...ABB Drives Modbus Protocol Manual RS 485 Adapter Module FSCA 01...
Страница 2: ......
Страница 4: ......
Страница 6: ...Safety instructions 6...
Страница 22: ...Drive configuration 22...
Страница 24: ...Master configuration 24...
Страница 46: ...Communication 46...
Страница 50: ...Definitions 50...
Страница 51: ......