background image

20 

Sensyflow FMT200-ECO2

 THERMAL MASS FLOWMETER  |  OI/FMT200-ECO2-EN REV. H 

 

 

… 6  Commissioning 

 

… Parameter descriptions 

 

‘Analog output’ Registration Tab 

 

1

  ‘Configure’ area, selection of the parameters to be configured via check 

box 

 

 / 

.  

2

  Display of the currently set values 

 

3

  Display of the newly selected values 

 

Figure 15:  Parameterization program, ‘Analog Output’ Registration Tab 

 
This tab is used to configure the analog output. For the sake of transparency, both the current and amended values are displayed at 
the same time. 
•  The parameters to be changed should be selected using the check box 

 

 and the values changed in the entry field. 

•  The changed values are saved to the sensor using the 

‘Accept’

 button. 

 

The sensor is restarted and initialized (LED on the transmitter blinks red). No measured values are displayed during initialization. 

 

 

 

 

Содержание FMT200-ECO2

Страница 1: ...00 ECO2 is a very compact and highly dynamic mass flowmeter for air The Sensyflow FMT200 ECO2 enables direct mass or standard volume flow measurement in pneumatic applications for example for the cont...

Страница 2: ...ll the sensor 9 Electrical connections 10 Terminal layout 10 Electrical data for inputs and outputs 10 Parameterize 11 6 Commissioning 12 Checks prior to commissioning 12 Switching on the power supply...

Страница 3: ...to the product may only be performed if expressly permitted by these instructions Information and symbols on the product must be observed These may not be removed and must be fully legible at all time...

Страница 4: ...between the product and your network or any other network as the case may be Operator shall establish and maintain any appropriate measures such as but not limited to the installation of firewalls app...

Страница 5: ...bar abs High pressure version 16 102 kPa 16 bar abs Process connections Small flange adapter ISO KF flange screwed connection G in G in G in G 1 in Legris hose adapter Transair adapter Wetted materia...

Страница 6: ...m resistor is maintained at a constant overtemperature in relation to an unheated platinum sensor inside the gas flow The heating power required for maintaining the overtemperature depends directly on...

Страница 7: ...corrugated cardboard and place it in a box of sufficient size lined with a shock absorbing material e g foam rubber The thickness of the padding should be appropriate for the device weight and type o...

Страница 8: ...mounting position can be selected Inlet sections To prevent negative effects on measuring accuracy the ISO KF flange DN 25 Transair G in and G 1 should be provided in the inlet sections when using the...

Страница 9: ...the small flange adapter DN 25 decreasing approx quadratically at smaller flow rates Installing the sensor Before installing the sensor observe the following points The ambient conditions at the insta...

Страница 10: ...alog output signal 2 Brown RS 232C TxD transmi data 3 Green Pulse frequency output signal 4 Yellow Power supply 24 V DC 5 Gray Power supply GND 6 Pink RS 232C RxD receive data 7 Blue Analog output GND...

Страница 11: ...op bits 1 Parity None Data bits 8 Parameterize The Sensyflow FMT200 ECO2 can simultaneously operate one analog output current 0 4 to 20 mA or voltage 0 to 5 10 V one digital output frequency pulse ala...

Страница 12: ...anges and output signals in line with requirements 6 Commissioning Checks prior to commissioning The following points must be checked before commissioning the device Correct wiring in accordance with...

Страница 13: ...the PC laptop using the D Sub adapter If no RS232 interface is available additionally use the USB RS232 adapter 2 Power up the power supply of the sensor 3 To launch the parameterization program execu...

Страница 14: ...rview CURRENT DEVICE DATA ANALOG OUTPUT CURRENT 0 to 20 mA 4 to 20 mA VOLTAGE 0 to 10 V 0 to 5 V DIGITAL OUTPUT FREQUENCY OUTPUT 10 to 1000 Hz 1 to 100 Hz PULSE OUTPUT VARIABLE 1 to 2500 Hz SWITCH OUT...

Страница 15: ...umed 1 The parameterization data must be resaved by selecting the Accept button Wait until the symbol indicating that a program is running disappears and the status indication for the initialization p...

Страница 16: ...multiple of kg h Parameter Description Unit Name of the unit text field Factor Enter the factor of the unit in kg h Decimal numbers must be entered using a period rather than a comma Standard conditi...

Страница 17: ...screen 1 Menu bar 2 Registration Tab 3 Device identification 4 Current measured value 5 Standard condition parameter display when selecting a volume unit 6 Status bar 7 Sensor connection status 8 Ana...

Страница 18: ...f the current measured value up scales the set upper limit the bar has a red color If the current measured value is within the set limits the bar has a green color Standard condition Figure 11 Standar...

Страница 19: ...Set flow rate per impulse Duration Set impulse length Polarity Set polarity low high for the impulse Switch option Figure 14 Switch The current measured value is monitored for fluctuation either side...

Страница 20: ...Parameterization program Analog Output Registration Tab This tab is used to configure the analog output For the sake of transparency both the current and amended values are displayed at the same time...

Страница 21: ...he maximum current maximum voltage on the analog output Low flow Set the flow rate below which no measurement is made measured value 0 Filter factor Set the time constant for the damping of the output...

Страница 22: ...meterization program Digital Output Registration Tab This tab is used to configure the digital output For the sake of transparency both the current and amended values are displayed at the same time Th...

Страница 23: ...quency corresponds to a flow rate of 100 of the set upper range value Parameter Description min Enter the frequency for 0 flow rate max Enter the frequency for 100 flow rate maximum 2500 Hz Impulse ou...

Страница 24: ...status LED on the sensor Status LED on the transmitter The status LED on the transmitter indicates the operating condition of the device and displays possible faults LED Description Continuous green l...

Страница 25: ...nor should they be bent or damaged in any other way Any attempts to clean the sensor that go beyond the steps described above may cause destruction to the sensor Cleaning through blow out 1 Remove the...

Страница 26: ...sideration If the device is to be used at another location the device should preferably be packaged in its original packing so that it cannot be damaged Observe the notices in Returning devices on pag...

Страница 27: ...Sensyflow FMT200 ECO2 THERMAL MASS FLOWMETER OI FMT200 ECO2 EN REV H 27 11 Accessories Sensor Figure 21 Flowmeter sensor FMT200 ECO2 with mounted small flange adapter...

Страница 28: ...Process connection KF DN 25 to adapt inlet run and outlet run includes 2 clamp rings and 2 sealing rings Inlet section 10 D both sides with KF DN 25 connection Outlet section 5 D both sides with KF DN...

Страница 29: ...ter pair for inlet and outlet inlet adapter with high tech flow conditioner Legris hose adapter pair Screwed connection G in simultaneous connection for Transair system 25 mm pair Transair adapter 25...

Страница 30: ...ification Note The device data sheet is available in the ABB download area at www abb com flow 13 Additional documents Note All documentation declarations of conformity and certificates are available...

Страница 31: ...ils Company Address Contact person Telephone Fax Email Device details Type Serial no Reason for the return description of the defect Was this device used in conjunction with substances which pose a th...

Страница 32: ...otice With regard to purchase orders the agreed particulars shall prevail ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document We res...

Отзывы: