Parameterization
110 FEX300,
FEX500
OI/FEX300/FEX500-EN
7.4.7 Menü:
Communication
Menu / Parameter
Value range
Description
Communication
HART
Select the "HART" submenu.
Cyclic Data Out
Select the "Cyclic Data Out" submenu.
Service Port
Select the "Service Port" submenu.
PROFIBUS
Select the "PROFIBUS" submenu.
The menu is displayed only for devices with
PROFIBUS PA.
FIELDBUS Foundation
Select the "FF" submenu.
The menu is displayed only for devices with
FOUNDATION Fieldbus.
Communication /
HART
Device Address
0 ... 15
Select the HART device address.
The HART protocol has provisions for creating a bus
with up to 15 devices (1 ... 15).
Important (Notice)
If an address greater than 0 is set, the device
operates in Multidrop mode, i.e., the current
output is fixed at 4 mA and there is only HART
communication over the current output.
Default setting: 0
HART TAG
8 characters, uppercase only,
no special characters.
Enter a HART TAG number as unique identifier for the
device.
HART Descriptor
16 characters, uppercase
only, no special characters.
Enter a HART descriptor.
HART Message
Display only.
Display of the alphanumeric TAG number.
HART Manf. ID
Display only.
Display of the HART manufacturer ID.
ABB = 26
HART Device ID
Display only.
Display of the HART device ID.
FEX300 / FEX500 = 30
Last HART Command
Display only.
Display of the most recently sent HART command.
Communication /
Cyclic Data Out
Cyclic Upd. Rate
0,2 ... 3600 sec
Set the interval for data output via the infrared service
port
Default setting: 1 sec
Important (Notice)
For detailed information about how to use the
infrared service port refer to the separate
operating instructions OI/FZA100.
Cyclic Upd. Select
Select the "Cyclic Upd. Select" submenu.
italics
= Parameter can only be viewed at the "Advanced" password level.
1) Parameter / menu only available for FEP500 / FEH500.