Parameterization
100 FEX300,
FEX500
OI/FEX300/FEX500-EN
Menu / Parameter
Value range
Description
Device Setup / Transmitter / Low Flow Cut Off
Flow Cut Off Level
0 ... 10 %
Select the switching threshold for leak flow volume
monitoring.
If the flowrate is below the switching threshold for the
leak flow volume, the flow is not measured. The
current output is set to zero.
Default setting: 1%
Hysteresis
0 ... 50 %
Set the hysteresis for the leak flow volume.
Device Setup / Transmitter / Operating Mode
Meter Mode
Forward and Reverse
Set the measuring direction for the flowmeter sensor.
• „Forward only“: The device measures only forward
direction.
• „Forward and Reverse“: The device measures and
totalizes both directions.
Default setting: „Forward and Reverse“
Flow Indication
Normal, Reverse
Inverts the flow direction displayed.
Default setting: „Normal“
Device Setup / Transmitter / System Zero
Manual Adjust
-50 ... +50 mm/s
Enter the flow velocity for system zero.
Auto Adjust
Starts the automatic zero adjustment.
Important (Notice)
Prior to starting the zero adjustment, make sure
that:
• There is no flow through the flowmeter sensor
(close all valves, shut-off devices, etc.)
• The flowmeter sensor is completely filled with
the fluid to be measured.
italics
= Parameter can only be viewed at the "Advanced" password level.
1) Parameter / menu only available for FEP500 / FEH500.