Drive configuration
14
Table 1. FENA-01 Configuration Parameters - Group A (Group 1)*
Par.
no.
Parameter name
Alternative settings
Default
setting
1
FBA TYPE
(Read-only)
ETHERNET
2
PROTOCOL/
PROFILE
Modbus/TCP:
0
ABB Drives Classic
1
ABB Drives Enhanced
2
Transparent 16-bit
3
Transparent 32-bit
EtherNet/IP:
100
ODVA AC/DC Drive
101
ABB Drives Profile
102
Transparent 16-bit
103
Transparent 32-bit
0
Modbus/TCP
3
COMMRATE
0
Auto-negotiate;
1
100 Mbps, Full Duplex
2
100 Mbps, Half Duplex
3
10 Mbps, Full Duplex
4
10 Mbps, Half Duplex
0
Auto-negotiate
4
IP CONFIGURATION
0
Static IP
1
Dynamic IP (DHCP)
1
Dynamic IP
(DHCP)
5
IP ADDRESS 1
0…255
0
6
IP ADDRESS 2
0…255
0
7
IP ADDRESS 3
0…255
0
8
IP ADDRESS 4
0…255
0
9
SUBNET CIDR
1…31
1
10
GW ADDRESS 1
0…255
0
11
GW ADDRESS 2
0…255
0
12
GW ADDRESS 3
0…255
0
13
GW ADDRESS 4
0…255
0