APPENDIX: List of FBVI-2U4-4T points
The
FBVI-2U4-4T
strategy
is available in both Imperial and Metric units.
The tables in this Appendix list and describe the points in the
Strategy
and gives the units in each
Strategy
type along with the default value in that
Strategy
type.
HARDWARE POINTS (I/O)
ANALOG
POINT POINT TYPE OBJECTNAME
DESCRIPTION
IMPERIAL
UNITS
METRIC
UNITS
1
Analog Input
UI01
Room/Zone Temperature Sensor
° F
° C
2
Analog Input
UI02
Setpoint Adjust Potentiometer
Ohms
Ohms
3
Analog Input
UI03
Supply or Discharge Air
Temperature
° F
° C
4
Analog Input
UI04
CO2, Humidity, or Motion
Detection
Volts
Volts
8
Analog Input
UI08
Flowrate Sensor
Pascals
Pascals
14
Analog
Output
AO14
Modulating Heat Stage 1
%
%
15
Analog
Output
AO15
Modulating Heat Stage 2 or
Variable Fan Speed Control
%
%
16
Analog
Output
AO16
Damper Commanded Position
%
%
DIGITAL
POINT POINT TYPE
OBJECTNAME DESCRIPTION
Active
Text
Inactive
Text
09
Digital
Output
DO09
Heating Stage 1 or Tri-State
Heating Valve Open
On
Off
10
Digital
Output
DO10
Heating Stage 2 or Tri-State
Heating Valve Close
On
Off
11
Digital
Output
DO11
Heating Stage 3
On
Off
12
Digital
Output
DO12
Series/Parallel On/Off Fan
On
Off