If the discharge air temperature is configured and DualMax control is enabled:
o
As heating demand rises from 0-50%, the discharge air temperature shall be reset
upwards, to a maximum of 20 deg above zone temperature. The stages of heat shall be
enabled to maintain a discharge air temperature setpoint.
o
As heating demand rises from 51-100%, the airflow setpoint shall reset from the
minHeatFlowStpt (A230)
to the
maxHeatFlowStpt (A229)
flow.
o
The duct coil shall control the VAV discharge air temperature to the setpoint. The duct coil
shall not directly control zone temperature.