FBVi-2U4-4T |
FBVI-2U4-4T Contr
©ABB 2021 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
76
M
AN
01
48
re
v 5
FAN CONTROL
Parallel Single Speed Fan Option
During the occupied mode, the intermittent single speed fan will be energized in the heating mode.
The fan control matrix is as follows:
MODE
COOLING
DEADBAND
HEATING
Occupied
Off
Off
On
Unoccupied
Off
Off
On
Warm-up
Off
Off
Off
Standby
Off
Off
On
Series Single Speed Fan Option
The fan will operate continuously whenever the unit is in the occupied state, or in another state and in
the cooling or heating mode. The fan control matrix is as follows:
MODE
COOLING
DEADBAND
HEATING
Occupied
On
On
On
Unoccupied
On
Off
On
Warm-up
N/A
On
On
Standby
On
On
On