40
Reset
Anomalies
: setting the digital input “Trip Signal and Reset Anomalies (default DI 11) on high
the function is executed. Reset is available when an anomaly is present.
Reset Anomalies clear the anomaly indication only; if the anomaly condition persists will be indicated
again.
Firmware Download
: enables you to upgrade the firmware version on the IED, it opens a browse
window to choose the file .out to download. Available when an active communication link has been
established with the IED, and only in help mode.
Procedure
Shut down the IED power supply and wait until Ready indication and position sensor indication
goes off.
Close (arrow to ON) all I1 dip switches (from I1-1 to I1-5) and set JP6 (insert jumper) to define
full duplex communication mode, refer to 1VCD600132, figure 1, motherboard layout.
Power up the IED (please note that in this mode the CB HMI control panel will not light up)
Select Firmware Download from CoT, browse for file, launch with Open in browse window.
On completion of updating the firmware version, exit and re-launch the configuration tool, power
down the IED and reconfigure it to half duplex, removing JP6 and put I1 dip switches in off
position or according to required functionalities.
Fig. 24
Whole Calibration Factors
: with a pop-up window, this function provides the possibility of calibrating
all the analog channels (r. IED electronics) by introducing a numerical correction factor.
Calibration Parameters
: reads all the calibration parameters from the IED, i.e. the correction
factors for phase 1, 2, 3 and phase shift in respect of phase 1 stored during secondary calibration.
Anomalies sub-Menu
: enables you to read (
Anomalies List
) all active anomalies from the IED
for information to ABB service and to reset (
Reset
Anomalies
) the Anomaly signalling, clearing
the list and turning off the blinking LED “No Anomaly” on the CB HMI. Available when an active
communication link has been established with the IED.