The IEDs' bus connections are ready-made when the configuration work is
started and need not to be set separately.
4.
In the
Tools
menu, change the user level to "Expert".
5.
Open the IED's
Properties
window and check that all the
DataFlowGeneration options have the value TRUE before the first SCL
export from the CCT600 project.
If the value is FALSE, the dataflow is not updated when the SCL file is
imported back to the project.
6.
To allow the event clients appear under LD0.LLN0 for every report control
block, update the data flow from the tool.
GUID-270775BC-0707-4E6A-B1C4-62CF3BB10F50 V1 EN
Figure 27:
IEC 61850 event reporting clients
6.2
Defining server IEDs
Do this task only for server IEDs, not for client IEDs.
1.
In CCT600, open the
Project Navigator
and select an IED from the submenu.
2.
In the
Properties
window below the
Project Navigator
, type any text string
to
Partner IP Address Regex
field to define that the IED is not an IEC
61850 client.
1MRS757255 B
Section 6
Required CCT600 project modifications
Breaker Integrated Protection RBX615
43
Engineering Guide