Section 6
Required CCT600 project modifications
When the IED configurations are changed using CCT600, some preparations are
required when starting a project and importing the 615 series IED data model to the
tool for the first time. The imported or exported file can be an SCD or CID file.
•
The default 615 series IED SCL export from PCM600 contains five default
client definitions, Client1...Client5, which are used by all the report control
blocks. The MicroSCADA and COM600 clients are able to use the client
definitions directly.
In other cases, import the ICD file describing the client data model to the
project, and attach the file to the same IEC 61850 subnetwork in
communication section view.
•
Attach the new client to report control blocks.
•
Keep the IEC 61850 event reporting configuration consistent with the CCT600
project.
1.
Create the bus connections for the IEC 61850 clients.
2.
Define that the server IEDs are not IEC 61850 clients.
3.
Check that in IED Properties, all the DataFlowGeneration options have
the value TRUE before the first SCL file export from CCT600.
For more information, see CCT600 documentation.
6.1
Attaching the IEC 61850 clients to the bus
1.
In CCT600, open the
Project Navigator
and select an IEC 61850 client from
the submenu.
2.
In the
Properties
window below the
Project Navigator
, select the bus from
the
Bus Connection
list to attach the IEC 61850 client to the bus.
1MRS757255 B
Section 6
Required CCT600 project modifications
Breaker Integrated Protection RBX615
41
Engineering Guide