0 5 . PR OTEC TI O N FU N C TI O NS 45
—
35 Long start protection
Long start protection
The long start protection protects motor against
locked or stalled rotor in starting state. M10x
detects the current after a start command, and
signals a fault when current continuously exceeds
a separately set threshold of the period of start
time.
Function
Setting range
0=Disabled 1=Enabled
Default value
Disabled
Step value
1
Long start trip level (Locked rotor level)
Setting range
120-800%
Default value
120%
Step value
10%
Long start trip delay
Setting range
0-250sec
Default value
10sec
Step value
1sec
Trip reset mode
Setting range
2=Local 3=Remote 4=Remote and Local
Default value
4
Step value
1
—
Table 32 Long start protection parameters
See
'
M10x parameters description
'
manual for parameters explanation.