Name
Pin
Description
CCLI
X4:6
Contactor control voltage input
CCA
X4:7
Contactor control A
DI6(F_Ca)
X1:5
Contactor control A feedback
DI5(Loc/R)
X1:6
Local/remote control switch input
—
Table 25 Contactor feeder contactor control interface
—
28 Control circuit for contactor feeder
Contactor feeder
Contactor feeder in M10x is designed for
symmetric 3 phase load or single phase load. All
measurement, control and protection features
which are available to NR-DOL are available to
contactor feeder load.
Unlike the NR-DOL logic in which current feedback
is a built in feature, current feedback is no longer
required for motor status verification in contactor
feeder control.
* The assigned DI and PIN code may change in actual design
Operating sequence
• Starting Sequence: Motor is stopped
and ready to start
→
START command
(Start 1) received
→
Internal CCA contact closed
and remain closed
→
Feedback received
• Stopping Sequence: Motor is running
→
STOP command received
→
Internal CCA
contact open
→
Feedback received
Contactor feedback is used for verifica-
tion of the motor status. Any unex-
pected feedback results in alarm or fault.
Contactor feedback can be disabled
through parameter. The feedback time is
adjustable.