2TFP900034A1001 ECN000087106 Rev. A
Ekip E-Hub | 21
DI setting
Click
IO setting
to enter I/O setting page, then select
Digital
tab to configure DI
channels.
Powering and Insulation
Parameters
Description
Channel
8 Channels
Input type
Sink (Wet Contact)/Counter
Wet Contact Input
Logic 0: 0 ~ 5 VDC
Logic 1: 11 ~ 30 VDC
Rated Voltage
12/ 24 VDC
Rated Input Current
>
5mA@ 12VDC
>
10mA@ 24VDC
Over Voltage Protection
+40VDC
Isolation Voltage
2000VDC
DI could be configured as Pulse meter or Open/Close contact.
Pulse meter
: measuring value will
be increased one weight at each pulse
Open/Close contact
:
digital value 0 and 1 will be transferred into meaningful words set
in
status 0
and
status 1
.
Fig. 16
Parameters
Parameters
Description
Default
Name
DI channel name
DI Channel No.
Input type
DI input types for this channel:
Pulse meter
Open/Close contact
Pulse meter
Unit
Unit for the measurement
N/A
Pulse weight
Increment for Pulse meter.
0.1
Status 0
For Open/Close contact type: Meaning of status
0
Status 0
Status 1
For Open/Close contact type: Meaning of status
1
Status 1
NOTE
: Please configure the DI channels according to the real environment. The
DI channels’ data will be upload to the cloud after finishing the provision
process. If there is type changing in the DI channel, please do a re-provisioning
process to make the changes valid.