7.
Open Maintenance Bypass (IA1) by turning it to position “OFF”. The load is now supplied by the static
bypass of all three Modules. Check LED-indicators on control panels.
8.
Transfer load to Inverter-
Mode by means of COMMAND “LOAD TO INVERTER” on any one of
control panels. On LCD: “LOAD PROTECTED” will appear and the LED
-indicator will indicate as
shown below:
LED Indicator
Colour
LINE 1
Green
LINE 2
Green
BYPASS
OFF
INVERTER
Green
BATTERY
Green
THE LOAD IS NOW PROTECTED BY THE DPA UPScale