Section-2
04-3006_S2_OPM_ABB_DPA_UPSCALE_RI_10-80kW_EN_150316.doc
Page 12/14 ABB
Modifications reserved
2.3
BATTERY CONNECTIONS
2.3.1 INTERNAL BATTERY MODULES
The followings models have internal battery modules:
DPA UPScale RI11
DPA UPScale RI12
DPA UPScale RI22
DPA UPScale RI24
To achieve a correct cabling of the internal batteries modules, refer to the below drawings which show the various
possible battery configurations and the diagrams in the on the next pages and listed here:
Assembling: S20_0018C Electric Diagram Battery Cabling 2 x(1x50) RI UPScale
Assembling: S20_0019B Electric Diagram Battery Cabling 2 x(1x40) RI UPScale
Assembling: S20_0020C Electric Diagram Battery Cabling 2 x(2x40) RI UPScale
NOTE
:
For UPS-Systems DPA UPScale M-10kW, it is allowed to use 20-50 (only even numbers) of 12V-battery blocks
depending the power sourced on the output
For UPS-Systems DPA UPScale M-20kW, it is allowed to use 30-50 (only even numbers) of 12V-battery blocks
depending the power sourced on the output
IMPORTANT
: For max. battery autonomies with the corresponding the output power range and no. of battery
blocks per string, refer to Section 10.5 , page 8
NOTE
: Set-up the correct number of battery blocks on Control Panel (Menu: Service-Set-Up).
DPA UPScale RI 11
DPA UPScale RI 12
DPA UPScale RI 12
(
1x40)x7Ah
(1x50)x7Ah
(2x40)x7Ah
Module
Module
10
x7
Ah
10
x7
Ah
10
x7
Ah
10
x7
Ah
10
x7
Ah
10
x7
Ah
2x5
x
7Ah
10
x7
Ah
10
x7
Ah
10
x7
Ah
10
x7
Ah
10
x7
Ah
10
x7
Ah
Module
10
x7
Ah
10
x7
Ah
10
x7
Ah
10
x7
Ah
Содержание DPA Upscale RI Series
Страница 27: ......
Страница 28: ......
Страница 29: ......
Страница 31: ......
Страница 32: ......
Страница 33: ......
Страница 35: ......
Страница 36: ......
Страница 37: ......
Страница 39: ......
Страница 40: ......
Страница 41: ......
Страница 43: ......
Страница 44: ......
Страница 45: ......
Страница 47: ......
Страница 48: ......
Страница 49: ......
Страница 51: ......
Страница 52: ......
Страница 53: ......