46
Technical Data
General
Standards
IEC 62052-11, IEC 62053-21,
EN 50470-1, EN 50470-3
Voltage
230 V AC
Voltage range
-23% to +20%
Reference (Max) current
10 (80) A
Start current
25 mA
Power consumption of current circuit < 1,8 VA
Frequency
50/60 Hz (±5%)
Accuracy of measurement
Class B (Cl 1, ±1%)
Memory backup
EEPROM
Temperature range
-40 to +55
o
C
Material of front cover
Polycarbonate
Material of back cover
Polycarbonate/glass fiber
Resistance to heat and fire
IEC 695-2-1
Protection against penetration of
IP 20 *)
dust and water
Connection area, current connecting 4 – 25 mm
2
terminals
Pulse output
Standard
IEC 62053-1 (SO)
Connection area, connecting terminal 0.5 – 2.5 mm
2
Recommended torque value
0.5 Nm
External pulse voltage
5 – 40 V DC
Max. current
100 mA
Pulse length
100 ms
Pulse frequency
100 imp/kWh
LED
Pulse frequency
1000 imp/kWh
Pulse length
40 ms
Display
Type
LCD with 6 digits
Digits height
6 mm
Clock
Standard
IEC 62054-21
Clock backup
SuperCap. 48h
Clock accuracy
Net supply : ±5s / 30 days
(at normal frequency and
operating conditions)
*) To comply with the protection requirements the meter must be
mounted in a class IP 51 enclosure or better, according to IEC 60529.
Содержание DELTAsingle
Страница 2: ......
Страница 14: ...12 ...
Страница 26: ...24 ...
Страница 38: ...36 ...
Страница 50: ...48 ...
Страница 73: ...72 ...
Страница 85: ...84 ...
Страница 97: ...96 ...
Страница 120: ...120 ...
Страница 132: ...132 ...
Страница 155: ...156 ...
Страница 156: ......
Страница 160: ...161 ...