45
Pulse output (optional)
The pulse output, passive and polarity dependent,
needs a separate power supply and that the polarity is
correctly wired
9
. Pulses generated are proportional
to energy consumed.
Trouble Shooting
Check following carefully before contacting you vendor
Load indicator is not rotating
- the current going through the meter is too low
Load indicator is going anti clock wise
- the current is going through the meter backwards
No pulses given
(Meters with pulse output only)
- Separate power supply missing or not working
properly
- Wrong polarity
- Load is to low (too long time between the pulses)
Installation check / Error codes
Error code Reason
Recommended Action
100-107
Meter internal error
Contact supplier
300
Voltage exceeding
The meter can be damaged
maximum voltage
Reduce voltage immediately
301
Voltage below
Increase voltage to ensure the
minimum voltage
meters full functionality
302
Amperage exceeding The meter can be damaged
maximum amperage Reduce amperage immediately
303
Frequency is wrong
Check network frequency
501-502
Date / Time is missing Set correct date / time
700-705
Meter internal error
Contact supplier
For more details see: DELTAsingle User’s Manual.