![ABB DCS800 Скачать руководство пользователя страница 58](http://html.mh-extra.com/html/abb/dcs800/dcs800_installation-manual_3333058.webp)
58
Stripped part covered with
copper foil
Stripped cable
Conductive surface of the
screen exposed
Cable screen
−
Cut the screen at the midpoint of the bare part. Be careful not to cut
the conductors.
−
Turn the screen inside out to expose its conductive surface.
−
Cover the turned screen and the stripped cable with copper foil to
keep the shielding continuous.
Note:
The ground wire (if present) must not be cut.
−
Push the two parts of the lead-through plate together so that the
conductive cushions press tightly round the foil covered screen.
5.
Lock the two parts of the lead-through plate by tightening the positioning
screws.
6.
Top entry: If more than one cable go through a single grommet, the grommet
must be sealed by Loctite 5221 (catalogue number 25551).
Side
view
Top entry
Electrical Installation
3ADW000352R0101 DCS800-A Installation Manual e a
Содержание DCS800
Страница 1: ...DCS800 Installation Manual DCS800 A Enclosed Converters 18 to 9800 A 19600 A ...
Страница 26: ...26 Cabinet 400 mm width 600 mm depth Mechanical Installation 3ADW000352R0101 DCS800 A Installation Manual e a ...
Страница 69: ...69 Preventive Maintenance 3ADW000352R0101 DCS800 A Installation Manual e a ...